Chapter 6
Troubleshooting
221
6.3 Alarm Level
The alarms are classified to 3 types of levels by the content of the error.
Alarm level
ALM lamp
*ALM signal
Status when an
error occurred
Cancellation method
Message
OFF
No output
No stop
Alarm of maintenance output such as
battery voltage drop or the teaching tool
such as PC software
[Refer to Instruction Manual of each tool
for details.]
Operation
release
ON
Output
Servo OFF after
deceleration to
stop
Reset the alarm by the PIO or teaching
tool.
Cold start
ON
Output
Servo OFF after
deceleration to
stop
Software reset or power reconnection by
teaching tool.
Home return is required for any actuators
of other than simple absolute
specification.
Caution: Reset each alarm after identifying and removing the cause.
If the cause of the alarm cannot be removed or when the alarm cannot be reset
after removing the cause, please contact IAI.
If the same error occurs again after resetting the alarm, it means that the cause of
the alarm has not been removed.