3 generation of noise and/or vibration, 4 impossible communication – IAI America MSEP User Manual
Page 228
Chapter 6
Troubleshooting
220
6.2.3
Generation of noise and/or vibration
Situation
Possible cause
Check/Treatment
Generation of noise
and/or vibration from
actuator itself
Noise and vibration are generated by
many causes including the status of
load, the installation of the actuator, and
the rigidity of the unit on which the
actuator is installed.
Servo adjustment may improve the
situation.
[Refer to 5.3 Servo Adjustment.]
Vibrations of load
1) Acceleration/deceleration is set too
high.
2) The installation structure and/or the
installed load are easily affected by
acceleration/deceleration.
1) Decrease the settings of
acceleration/deceleration.
6.2.4
Impossible Communication
Situation
Possible cause
Check/Treatment
Not connectable with
host machine㩷
1) Communication rates do not match.
2) The machine number (station number)
is set to be duplicate with that of
another unit or out of the range.
3) Poor wiring or disconnection of
communication cable㩷
1) Set the communication rate to
match that of the host machine.
[Refer to the Instruction Manual of
the host unit.]
2) Correct the unit number (station
number) setting.
Machine numbers (station
numbers) vary depending on
communication modes. Refer to
3.4 Fieldbus Type Address Map
and the instruction manuals for
the host devices for the details.
3) Review the wiring again. Check if
termination resistances are
connected to network terminals
with correct values.
Check if the communication
power supply is established
properly for DeviceNet Type.
[Refer to the Instruction Manual of
the host unit.]