Chapter 6

Troubleshooting

220

6.2.3

Generation of noise and/or vibration

Situation

Possible cause

Check/Treatment

Generation of noise

and/or vibration from

actuator itself

Noise and vibration are generated by

many causes including the status of

load, the installation of the actuator, and

the rigidity of the unit on which the

actuator is installed.

Servo adjustment may improve the

situation.

[Refer to 5.3 Servo Adjustment.]

Vibrations of load

1) Acceleration/deceleration is set too

high.

2) The installation structure and/or the

installed load are easily affected by

acceleration/deceleration.

1) Decrease the settings of

acceleration/deceleration.

6.2.4

Impossible Communication

Situation

Possible cause

Check/Treatment

Not connectable with

host machine㩷

1) Communication rates do not match.

2) The machine number (station number)

is set to be duplicate with that of

another unit or out of the range.

3) Poor wiring or disconnection of

communication cable㩷

1) Set the communication rate to

match that of the host machine.

[Refer to the Instruction Manual of

the host unit.]

2) Correct the unit number (station

number) setting.

Machine numbers (station

numbers) vary depending on

communication modes. Refer to

3.4 Fieldbus Type Address Map

and the instruction manuals for

the host devices for the details.

3) Review the wiring again. Check if

termination resistances are

connected to network terminals

with correct values.

Check if the communication

power supply is established

properly for DeviceNet Type.

[Refer to the Instruction Manual of

the host unit.]