background image

Chapter 6

Troubleshooting

222

6.4 Alarm List

6.4.1

Gateway Alarm Codes

The alarm codes are read into b7 to b0 in Gateway Status Signal 0.

(Note) The alarm code shown on Gateway Parameter Setting Tool is applied with “8” on the

top of the alarm codes listed below. (Example) If the alarm code is 43, it will be shown

as 843.

Alarm

Code

Alarm Name

Cause/Treatment

43

Absolute Battery Charge

Voltage Drop

Cause

: The voltage of the absolute battery charger has dropped.

Treatment : Check the voltage of the 24V DC power supply.

Check the wire layout between the absolute battery box

and MSEP controller.

48

Decrease in Fan

Revolution

Cause

: The fan rotation speed has decreased for the cooling fan

on the main unit.

Treatment : It is considered that it is the end of the product life of the fan

(approximately 3 years). Replace the fan.

49

Time Notification Error

Cause

: It is an internal communication error of MSEP. The clock data

transfer from Gateway board to the driver board has failed.

Treatment : Turn the power OFF and reboot. If the same error occurs

again, please contact IAI.

4A

Real Time Clock

Operation Stop Detection

Cause

: Clock data has lost.

The clock data can be remained for approximately 10 days

after the power to the controller is turned OFF.

Treatment : Have the clock setting done from the Gateway Parameter

Setting Tool again.

4B

Real Time Clock Access

Error

Cause

: It is an internal error of MSEP. The clock data failed to be

acquired internally.

Treatment : Turn the power OFF and reboot. If the same error occurs

again, please contact IAI.

50

Fieldbus Communication

Error

(ERR-C)

Cause

: It is a Fieldbus link error. If the flip-flop is set in Gateway

Parameter Setting Tool during this error, the actuator is

stopped in the condition of the error and any command is

ignored until it receives a release signal.

Treatment : Check the settings for Fieldbus (node addresses,

communication speed, etc.) and wiring layout.

60

Master-Slave Axes

Communication Error

(ERR-T)

Cause

: It is an internal error of MSEP. The communication with the

driver board to connect each axis of the actuators was not

able to be established.

Treatment : It is considered that the driver board is not inserted or there

is a failure in the connection (connector is not inserted deep

enough).

61

Master-Slave Axes

Communication Internal

Error

(Sending)

Cause

: It is an internal error of MSEP. The communication with the

driver board to connect each axis of the actuators was not

able to be established.

Treatment : Turn the power OFF and reboot. If the same error occurs

again, please contact IAI.

62

Master-Slave Axes

Communication Internal

Error

(Receiving)

Cause

: It is an internal error of MSEP. The communication with the

driver board to connect each axis of the actuators was not

able to be established.

Treatment : Turn the power OFF and reboot. If the same error occurs

again, please contact IAI.

6A

Driver Board Operation

Pattern Error

Cause

: Operation modes which cannot be used together are

indicated.

Treatment : Set the operation modes again on Gateway Parameter

Setting Tool.

80

GW Parameter Error

Cause

: There is an error in Gateway parameters.

Treatment : Check the settings such as the number of connected axes

and operation mode on Gateway Parameter Setting Tool.