Chapter 4 Parameters

157

[26] Control device No. (extension motion control board output channel parameter No. 18)

No.

Parameter name

Unit

Input range

Default value

(reference)

18

Control device No.

Axis No.

0~99999999

0

This parameter sets main CPU control axis No. (XSEL-P/Q:1 to 6, XSEL-R/S: 1 to 8) that performs

extension motion control board slave operations. If the settings of parameters for each axis No. 167

and 168 and extension motion control board output channel parameters No. 1 and 18 are not correct,

error No. 531 “slave operation parameter error” and error No. 52D “Extension motion control board

main CPU axis control parameter error” occur.

* When this parameter is to be set, make sure to set 2 for output channel parameter No. 1, channel

usage.

[27] Servo ON completion check time (extension motion control board output channel parameter No. 31)

No.

Parameter name

Unit

Input range

Default value

(reference)

31

Servo ON completion check time

sec

1~9999

150

This parameter sets time-out for the servo ON completion signal from the slave driver.

[28] Home return completion check time (extension motion control board output channel parameter No. 32)

No.

Parameter name

Unit

Input range

Default value

(reference)

32

Home return completion check time

sec

1~9999

150

This parameter sets time-out for the home return completion signal from the slave driver.

[29] Positioning completion check time (extension motion control board output channel parameter No. 33)

No.

Parameter name

Unit

Input range

Default value

(reference)

33

Positioning completion check time

100msec

1~999

10

This parameter sets the time period from the positioning command transmission completion to the

positioning completion status turned ON.

[30] Servo ON signal OFF error detection delay time (extension motion control board output channel

parameter No. 34)

No.

Parameter name

Unit

Input range

Default value

(reference)

34

Servo ON signal OFF error detection delay

time

msec

1~5000

100

This parameter sets the detection time period from the servo ON signal to OFF signal.

[31] Alarm reset command signal output time (extension motion control board output channel parameter

No. 36)

No.

Parameter name

Unit

Input range

Default value

(reference)

36

Alarm reset command signal output time

msec

1~99

10

This parameter sets the slave driver alarm rest signal output time period.