AC Power Supplies

ReFlex Power™

4-8

M380056-01 Rev K

Voltage Line Transient

Less than 1% of full scale maximum excursion decaying to steady-state value,
within 0.1% of full scale, within 100ms for 10% line change

Auxiliary Output

The Auxiliary output tracks the primary AC Voltage output, 140 VAC range
only, at 22.6% of the output voltage. The Auxiliary Output is limited to 61VA,
31.6 VAC at 2 A maximum. The Auxiliary Output frequency is limited within the
range of 350-1000 Hz.

Remote Sense Capability

Remote sense shall compensate for at least 0.75V

RMS

per load line leg.

Opening the sense lines during operation shall not damage the module or the
load; module will continue to maintain output, but with reduced programming
accuracy to 5%. Misconnection of the sense leads shall not result in an output
voltage in excess of the over-voltage protection limit. Sense leads connected
with reversed polarity will result in shutdown of the output. Excessive load line
voltage drop will result in shutdown of the output.

Current Programming Range

0 to 102% of full scale

Current Digital Programming Accuracy

(0.5% + 0.75%/kHz) of full scale, at 25 °C, +/- 5 °C; from 2% to 102% of current
range

Current Digital Programming Resolution

6mA

Current Temperature Drift

0.05% of full scale/°C

Continuous Current

7A, maximum for 0-140VAC range;
3.5A, maximum for 0-280VAC range (Not to exceed 875 VA)

Allowable Transient Current

10A

RMS

, maximum for 0-140VAC range;

5A

RMS

, maximum for 0-280VAC range;

time duration of 0.5s, maximum