Mainframe – AMETEK ReFlex User Manual

Page 47

background image

Mainframe

ReFlex Power™

2-12

M380056-01 Rev J

parallel. The load that would be applied to a particular AC/DC input line is
dependent on the location of the modules in the Mainframe slots.

The slots are grouped in sets of four: Slot 1-4, Slot 5-8, and Slot 9-12. Slot 1 is
the left-most slot, as viewed from the front (refer to Figure 2-5. Each of the
backplane connectors of a set of four slots is connected in parallel and is
supplied by one pair of the AC/DC input lines. In a double-width and triple-width
module, the module connector is located so that it mates to a backplane
connector in the right-most slot, as viewed from the front of the Mainframe. Refer
to Figure 2-4 for a diagram showing the power distribution from the input
connector to the twelve Mainframe slots.

AC/DC
Input

L1

L1-RTN

L2

L2-RTN

L3

L3-RTN

GND

Slot 1 Power

Slot 2 Power

Slot 3 Power

Slot 4 Power

Slot 5 Power

Slot 6 Power

Slot 7 Power

Slot 8 Power

Slot 9 Power

Slot 10 Power

Slot 11 Power

Slot 12 Power

L1 Power to Slots 1-4

L2 Power to Slots 5-8

L3 Power to Slots 9-12

Safety
GND

Mainframe

Figure 2-4. Input Power Distribution (Slot 1 at top is left-most slot of Mainframe

front view, as in Figure 2-5).