Standalone configuration operation check, Parallel configuration operation check – AMETEK ReFlex User Manual
Page 263
DC Power Supplies
ReFlex Power™
6-60
M380056-01 Rev K
12. The DC power supply module should respond with its
identification string. The default settings of the module will not be
affected.
S
TANDALONE
C
ONFIGURATION
O
PERATION
C
HECK
1. Connect the output for standalone operation per the section,
Standalone Configuration.
2. Connect appropriate instrumentation for measuring the output
voltage and current, as well as a load.
3. Perform the power-on verification test per the section, Power-On
Check.
4. Turn on the isolation and remote sense relays, turn on the output
converter, and program full-scale voltage and current with the
following commands:
*RST[n]
OUTP[n]:ISOL 1
OUTP[n]:SENS 1
OUTP[n]:STAT 1
SOUR[n]:VOLT
SOUR[n]:CURR
5. Measure the output voltage and current with the external
instruments.
6. Ensure that the actual values of the output parameters are within
specifications of the programmed values.
7. Query the values of the output parameters with the following
commands:
MEAS[n]:VOLT?
MEAS[n]:CURR?
8. Ensure that the readback values of the output parameters are
within specifications of the actual values.
9. Turn off the output with the following command:
*RST[n]
P
ARALLEL
C
ONFIGURATION
O
PERATION
C
HECK
1. Before attempting to verify parallel operation, perform the power-
on test of the individual modules per the section, Power-On
Check, and then the standalone operation test per section,
Standalone Configuration.
2. Connect the outputs for parallel operation per the section, Parallel
Configuration. Ensure that the outputs and remote sense are