When an DC power supply module is first powered on, the following
parameters are set to factory default values:
•
Output configuration: standalone
•
Output voltage: 0V
•
Output current: 0A
•
Overvoltage protection (OVP): 110% of full-scale voltage;
programmable mode
•
Undervoltage protection (UVP): 0V
•
Overcurrent protection (OCP): 120% of full-scale current;
programmable mode
•
Output state: off
•
Output isolation and remote sense relays: open
R
ESET
C
ONDITIONS
If a module is reset with the SCPI command, *RST[n], (where n is the module
address), the following default conditions are set:
•
Output configuration: unchanged
•
Output voltage: 0V
•
Output current: 0A
•
Overvoltage protection (OVP): 110% of full-scale voltage;
programmable mode
•
Undervoltage protection (UVP): 0V
•
Overcurrent protection (OCP): 120% of full-scale current;
programmable mode
•
Output state: off
•
Output isolation and remote sense relays: open
•
All status reporting data structures are cleared; enable-masks
are not cleared.
6.5.6
I
NITIAL
F
UNCTIONAL
T
ESTS
P
OWER
-O
N
C
HECK
1. Ensure that the AC/DC input service is disconnected.
2. Install the interface cable between the host controller and the
ReFlex Power™ Controller module.
3. Connect an appropriate output load to the DC power supply
module.