beautypg.com

AMETEK ReFlex User Manual

Page 51

background image

Mainframe

ReFlex Power™

2-16

M380056-01 Rev J

Table 2-2. Module Backplane Slot Connections

Module Model

Width

Number

of Slots

Occupied

Slot Supplying

Input Power

Maximum Input

Current

(at 103.5VAC and

full load)

RFP-C1LAN-000-xxxx

single

1

single

0.2A

RFP-F1000-001-xxxx

single

1

single

2.8A

RFP-D1016-021-xxxx
RFP-D1065-5A1-xxxx

single

1

single

4A

RFP-D2033-030-xxxx
RFP-D2050-020-xxxx
RFP-D2050-025-xxxx
RFP-D2120-8A3-xxxx

RFP-D2450-2A3-xxxx

double

2

right-most

12A

RFP-A30XK-875-xxxx

triple

3

right-most

12A

RFP-L3500-750-xxxx
RFP-L3500-375-xxxx

triple

3

right-most

1.1A

The maximum output power per single group of four slots is produced when two
HPDC 1kW modules are installed in the group. This sets the maximum
aggregate output power limit of the Mainframe at 6kW. The resultant maximum
current per input connector line and per input service line is presented in Table
2-3.
In general, to determine the actual input currents, the current requirements
of the modules that are installed in each group must be summed. This would
determine the requirement for the AC/DC input overcurrent protection current
rating.

This manual is related to the following products: