Table 7-1. Input Power Allocation

Input

Service

Phases

Input

Designation

Input

Connector

Pin

Input Service

Connection

Slot

Supplied

100/115/120VAC
200/208VAC
220/230/240VAC

1

L1

F

Phase

Slot 1-4

L1-RTN

E

Return

L2

A

Phase

Slot 5-8

L2-RTN

G

Return

L3

B

Phase

Slot 9-12

L3-RTN

C

Return

GND

D

Ground

Slot 1-12

Safety GND

Chassis GND Ground

Chassis

200/208VAC

3

Delta

L1

F

Phase-A

Slot 1-4

L1-RTN

E

Phase-B

L2

A

Phase-B

Slot 5-8

L2-RTN

G

Phase-C

L3

B

Phase-C

Slot 9-12

L3-RTN

C

Phase-A

GND

D

Ground

Slot 1-12

Safety GND

Chassis GND Ground

Chassis

200/208VAC
220/230/240VAC

3

Wye

L1

F

Phase-A

Slot 1-4

L1-RTN

E

Neutral

L2

A

Phase-B

Slot 5-8

L2-RTN

G

Neutral

L3

B

Phase-C

Slot 9-12

L3-RTN

C

Neutral

GND

D

Ground

Slot 1-12

Safety GND

Chassis GND Ground

Chassis

210-360VDC

DC

L1

F

Source

Slot 1-4

L1-RTN

E

Return

L2

A

Source

Slot 5-8

L2-RTN

G

Return

L3

B

Source

Slot 9-12

L3-RTN

C

Return

GND

D

Ground

Slot 1-12

Safety GND

Chassis GND Ground

Chassis

A plug/socket connector is provided on the rear panel of the
Mainframe for connecting the unit to the AC/DC power source. The
connector also provides a safety ground termination. The input power
cable should include a safety ground wire to connect the chassis of
the Mainframe to the safety ground of the AC/DC power source. Since