17 ldf calibration for voltage range high – AMETEK ReFlex User Manual
Page 151
AC Power Supplies
ReFlex Power™
4-66
M380056-01 Rev K
4.6.17
LDF
C
ALIBRATION FOR
V
OLTAGE
R
ANGE
H
IGH
The following procedure calibrates the Line drop fault supervisory.
1. Ensure that no load is connected to the output.
2. Issue clear and reset commands:
*CLS
*RST
3. Set the voltage range of the power supply to high
SOUR
4. Turn the unit on
OUTP
5. Program the output voltage to count 17000
CAL
6. Send the calibration command to start the internal calibration
CAL
7. Turn the unit off
OUTP
8. Send the system error query command to make sure calibration was successful.
SYST:ERR?
9. If there is no error returned at the system error query command then save the
calibration result with the following commands
CAL
CAL
CAL
10. Optional Commands:
Query the voltage calibration points:
CAL
11. Reset the unit
*RST