≤187.2VAC to ≥171.8VAC: linearly derated from 100% to 85% of rated power
≤171.8VAC to ≥153.7VAC: linearly derated from 85% to 75% of rated power

P

OWER

F

ACTOR

> 0.95 at full output load, >0. 65 at 20% output load, decreasing to >0.3 at
no load

E

FFICIENCY

RFP-D1016-021-XXXX: 78%, minimum at full output power
RFP-D1065-5A1-XXXX: 80%, minimum at full output power
RFP-D2033-030-XXXX: 80%, minimum at full output power
RFP-D2050-020-XXXX: 80%, minimum at full output power
RFP-D2050-025-XXXX: 80%, minimum at full output power
RFP-D2120-8A3-XXXX: 80%, minimum at full output power
RFP-D2450-2A3-XXXX: 80%, minimum at full output power

H

OLD

-U

P

T

IME

10ms, with dropout of AC input at full output power for 330W, 332W, 990W, 1000W,
and 1035W models.

8ms, with dropout of AC input at full output power for 1250W model.

F

RONT

P

ANEL

I

NDICATORS

OUTPUT (LED, green): output enabled and isolation relay closed

POWER (LED, green): input AC/DC power applied to module

FAULT (LED, red): internal abnormal operating condition detected; output disabled
and isolation relay opened

BUS (LED, green): internal bus communication established

6.3.6

I

NPUT

/O

UTPUT

C

ONNECTIONS

P

ARALLEL

G

ROUPING

Any module could be a master; adjacent modules to the right (when viewed
from front of Mainframe) of the master would be slaves; multiple groups of
paralleled modules could be present in the same Mainframe; paralleling could
be extended between Mainframes; internal control interface is automatically
configured; outputs must be externally hardwired in parallel; individual modules
could provide full rated output current when paralleled; only like-rated modules
could be paralleled.
RFP-D1016-021-XXXX, RFP-D1065-5A1-XXXX:

nine modules could be connected in parallel

RFP-D2033-030-XXXX, RFP-D2050-020-XXXX, RFP-D2050-025-XXXX,
RFP-D2120-8A3-XXXX, RFP-D2450-2A3-XXXX:

six modules could be connected in parallel