Input frequency range, Maximum output aggregate power, Power factor – AMETEK ReFlex User Manual
Page 40: 3 general characteristics, Mainframe slots, Module compatibility, Backplane connectors, Connector accessibility, Mainframe safety ground stud, 4 mechanical characteristics
ReFlex Power™
Mainframe
M380056-01 Rev J
2-5
I
NPUT
F
REQUENCY
R
ANGE
47-63Hz with 85-264VAC input; 380-420Hz with 85-132VAC input
M
AXIMUM
O
UTPUT
A
GGREGATE
P
OWER
The maximum aggregate output power is dependent on the AC/DC input voltage:
≥200VAC or ≥210VDC: 6,000W
<200V AC: 3,600W
P
OWER
F
ACTOR
Dependent on the individual modules installed
2.3.3
G
ENERAL
C
HARACTERISTICS
M
AINFRAME
S
LOTS
12 single-width module slots
M
ODULE
C
OMPATIBILITY
Accepts single-width, double-width, and triple-width modules;
1kW maximum output power per slot
B
ACKPLANE CONNECTORS
Circuit-Board mounted connectors with integral guide pins
C
ONNECTOR
A
CCESSIBILITY
AC/DC input connector and multi-Mainframe interconnect connectors are accessible
from the rear of the Mainframe;
backplane connectors are accessible from the front.
M
AINFRAME
S
AFETY
G
ROUND
S
TUD
8-32 stud for connection to the AC/DC utility safety ground
2.3.4
M
ECHANICAL
C
HARACTERISTICS
D
IMENSIONS
7” H x 19” W x 17” D, EIA RS-310 rack-mount 4U
W
EIGHT
11.6 lbs
M
OUNTING
P
ROVISIONS
Hole pattern for RETMA rack slides; front mounting flanges