4 general characteristics, Input current, Power factor – AMETEK ReFlex User Manual
Page 176: Efficiency, Front panel indicators, 5 input/output connections

ReFlex Power™
Fixed Power DC Power Supply
M380056-01 Rev J
5-7
5.3.4
G
ENERAL
C
HARACTERISTICS
I
NPUT
V
OLTAGE
R
ANGE
103.5-253VAC with AC input; 270VDC, nominal; 210VDC, minimum to 300VDC,
maximum; 314VDC, maximum for 2s; 364.5VDC, maximum for 450ms
I
NPUT
C
URRENT
Power factor corrected single-phase AC input; unipolar DC input; sinusoidal current
with AC input; continuous DC current with DC input.
At 103.5 VAC input and full power output, the input current is 2.75 A maximum.
P
OWER
F
ACTOR
> 0.95 at full output load, >0.75 at 20% output load, decreasing to 0.3 at no load
E
FFICIENCY
60% minimum
F
RONT
P
ANEL
I
NDICATORS
OUTPUT (LED, green): output enabled and isolation relay closed
POWER (LED, green): input AC/DC power applied to module
FAULT (LED, red): internal abnormal operating condition detected; output disabled
and isolation relay opened
BUS (LED, green): internal bus communication established
5.3.5
I
NPUT
/O
UTPUT
C
ONNECTIONS
O
UTPUT
I
SOLATION
Each voltage output is isolated from the input line, the other output voltages, and the
module case by at least 1 Meg Ohm.
O
UTPUT
R
ELAYS
Each output is provided with an isolation relay.