J4 analog control in – AMETEK ReFlex User Manual
Page 61
Mainframe
ReFlex Power™
2-26
M380056-01 Rev J
J4
A
NALOG
C
ONTROL
I
N
Refer to Figure 2-11 for a view of the ANALOG CTRL IN, J4, connector.
The pinout and functions of the connector are presented in Table 2-9. The
associated maximum wire gauge for connector terminations, and
recommended maximum wire lengths are presented in Table 2-10.
Figure 2-11. J4 Analog Control Input Connector, Mainframe Rear Panel View
Table 2-9. J4 ANALOG CTRL IN Connector Pinout
Pin
Name
Function
Signal Level
F
SYNCH-IN
Input/output: SYNC bus
differential signal with SYNC-L
RS-485 logic levels referenced
to module AGND
R
SYNCL-IN
Input/output: SYNC bus
differential signal with SYNC-H
RS-485 logic levels referenced
to module AGND
U
CURRH-IN
Input/output: CURR bus
differential signal with CURR-L
10V analog signal referenced to
module AGND
N
CURRL-IN
Input/output: CURR bus
differential signal with CURR-H
10V analog signal referenced to
module AGND
S
CMDH-IN
Output: CMD bus differential
signal with CMD-L
10V analog signal referenced to
module AGND
H
CMDL-IN
Output: CMD bus differential
signal with CMD-H
10V analog signal referenced to
module AGND
K
/FLTBUS-IN
Input/Output: summary fault
signal bus
5V digital signal referenced to
module AGND
T
AGND-IN
Analog signal reference
Module circuit common AGND
referenced to output return
(negative) terminal
J
CHAS-GND
Chassis ground
Chassis
A,C,D,
G,H,I,K
,L, M
-
Reserved
-