Part 3 maintenance – IAI America REXT User Manual
Page 397
Part 3 Maintenance
Chapter 1 T
roubleshooting
365
Part 3 Maintenance
(2) Cold start level
Code
Alarm name
Cause/action
0A1 Parameter error Cause: The input range of data in the parameter area is not appropriate.
(Example) This alarm generates when the magnitude relationship of a pair of
input values is clearly inappropriate, such as when the values of
soft limit + and soft limit – were input wrongly as 200.3 mm and 300
mm, respectively.
Action: Change the input data to appropriate values.
0A8 Unsupported
motor/encoder
type
Cause: The motor type or encoder type set by a parameter is not supported.
Action: If the alarm generates again after reconnecting the power, contact IAI.
0B4 Inconsistent
electrical angle
Cause: The position deviation counter has overflowed.
Action: Check the load conditions such as whether the work part is contacting any
nearby object and whether the brake is released.
If this alarm generated before confirmation of electrical angles (while phase Z
was not yet detected), a deviation overflow may be a possibility. If this is the
case, the motor wire may be broken or output from the encoder wire may be
abnormal. Check the cable connections.
0B7 Indeterminable
magnetic pole
(RACON only)
0B8 Excitation
detection error
(RPCON only)
This controller performs magnetic-pole phase detection (pole sensing) when the servo is
turned on for the first time after the power ON. This alarm indicates that the magnetic-pole
phase could not be recognized within the specified time.
Cause: [1] Loose or disconnected motor-extension cable connector
[2] Brake cannot be released on an actuator equipped with brake.
[3] Large motor load due to application of external force
[4] Large slide resistance of the actuator itself
Action: [1] Check the wiring condition of the motor-extension cable.
[2] Check the wiring condition of the brake cable. Also, turn on/off the brake
release switch and check if the brake makes “click” sounds.
[3] Check for abnormality in the assembly condition of mechanical parts.
[4] If the payload is normal, cut off the power and move the actuator by hand to
check the slide resistance.
If the actuator itself is suspected as the cause, please contact IAI.
0C8 Overcurrent
(RACON only)
Cause: The output current from the power-supply circuit became abnormally high.
This alarm should not generate in normal conditions of use. If it does,
deterioration of motor coil isolation is suspected.
Action: Measure the line resistances between motor connection wires U, V and W, and
the isolation resistance with respect to the ground, to check for deterioration of
isolation.
If you require the above measurements, please contact IAI.
0CA Overheat
This alarm indicates that the temperature around the power transistor or regenerative
resistor in the controller is excessively high (95qC or above).
Cause: [1] The ambient temperature is high.
[2] The regenerative energy is excessive. (In the case of an actuator installed
vertically, the deceleration setting for downward movement is too high.)
[3] A faulty part inside the controller
Action: [1] Lower the ambient temperature of the controller.
[2] Review the settings and decrease the deceleration.
If [1] and [2] do not apply, please contact IAI.
-397-