Part 1 Specification
Chapter 3 Gateway R unit
135
Part 1 Specification
[7] Read completed position number status – Axis (0)
The configuration of the completed position number register of axis (0) is shown below.
z
Query
Field name
RTU mode data
(8 bits)
Data length
(bytes)
Remarks
Header
None
-
Slave address
3F H
1
Fixed.
Function code
03 H
1
Starting address
(upper)
F7 H
Starting address
(lower)
0A H
2
Address of the completed position number of
axis (0)
Number of registers (upper)
00 H
Number of registers (lower)
01 H
2
Number of registers (1 register = 1 word): 1
Error check
(CRC)
Based on
calculation result
2
(92 A2)
Trailer
None
-
Total bytes
8
z
Response
Field name
RTU mode data
(8 bits)
Data length
(bytes)
Remarks
Header
None
-
Slave address
3F H
1
Fixed.
Function code
03 H
1
Data bytes
02 H
1
1-word register x 1 = 2 bytes
Data 1
(upper)
Arbitrary
Data 1
(lower)
Arbitrary
1 each for upper
and lower words
2
Completed position number data
Error check
(CRC)
Based on
calculation result
2
Trailer
None
-
Total bytes
7
z
Actual Example
Sent Query:
3F03F70A000192A2
Received Response: 3F03020003D180
(Explanation) The completed position number is “3.”
Address