Part 1 Specification
Chapter 3 Gateway R unit
132
Part 1 Specification
[4] Monitor current electrical current – Axis (1)
z
Query
Field name
RTU mode data
(8 bits)
Data length
(bytes)
Remarks
Header
None
-
Slave address
3F H
1
Fixed.
Function code
03 H
1
Starting address
(upper)
F7 H
Starting address
(lower)
0E H
2
Address of the current electrical current of axis
(1)
Number of registers (upper)
00 H
Number of registers (lower)
02 H
2
Number of registers (1 register = 1 word): 2
Error check
(CRC)
Based on
calculation result
2
(93 62)
Trailer
None
-
Total bytes
8
z
Response
Field name
RTU mode data
(8 bits)
Data length
(bytes)
Remarks
Header
None
-
Slave address
3F H
1
Fixed.
Function code
03 H
1
Data bytes
04 H
1
1-word register x 2 = 4 bytes
Data 1
(upper)
Arbitrary
Data 1
(lower)
Arbitrary
1 each for upper
and lower words
2
Lower word of the current electrical current
Data 2
(upper)
Arbitrary
Data 2
(lower)
Arbitrary
Same as above Upper word of the current electrical current
Error check
(CRC)
Based on
calculation result
2
Trailer
None
-
Total bytes
z
Actual Example
Sent Query:
3F03F70E00029362
Received Response: 3F030400260000C43B
(Explanation) x Lower word: 0026 H
x
Upper word: 0000 H
The electrical current data is indicated in unit of 1mA.
In other words, 00000026 H = 38 (decimal) o 38 mA
-156-