Part 1 Specification
Chapter 6 Extension unit
233
Part 1 Specification
6.2 Specifications
Model
REXT (main unit)
Power-supply voltage 24 VDC r 10%
Power-supply current
MAX 100 mA
Ambient operating temperature 0 to 40qC
Ambient operating humidity
95% RH max. (non-condensing)
Operating ambience
Free from corrosive gases and dust.
Surrounding storage
temperature
0 to 40qC
Surrounding storage humidity
95% RH max. (non-condensing)
Vibration resistance
XYZ directions:
10 to 57 Hz, half amplitude – 0.035 mm (continuous)
0.075 mm (intermittent)
57 to 150 Hz – 4.9 m/s
2
(continuous) / 9.8 m/s
2
(intermittent)
Environment
Impact resistance
XYZ directions: 147 mm/s
2
, 11 ms, half-sine wave pulse
Protection degree
IP20
Weight
140 g (main unit only)
Outer diameter
34 W x 100 H x 73.3 D [mm]
Caution
The total distance from the Gateway R unit to the downstream SIO link must not exceed 30 m.
When selecting the unit link cables and controller connection cables, make sure the total distance of SIO link does not
exceed 30 m.