3 connection diagram, Connection diagram, External device setup manual – IDEC High Performance Series User Manual
Page 652
Chapter 6
634
External Device Setup Manual
3.3
Connection Diagram
For the wiring diagram between the PLC and MICRO/I or Touch, refer to the PLC manual for PLC pin-outs. For connecting two or
more PLC units with the MICRO/I or Touch, refer to the diagram below.
3.3.1
RS422/485 2-wire system
- There is no pin number corresponding to TERM on the HG2G-S/-5S/-5F, HG3G/4G. When inserting a termination resis-
tor, use a communication switch. For the setting of the switch, refer to Chapter 1 "3 Important Points Regarding Wiring"
on page 19
- HG2G-5F, HG3G/4G Series uses only RDA and RDB when using RS422/485 2-wire, you don’t need to connect SDA or
SDB.
If connecting COM1 on the HG2G-5F, HG3G/4G to the external device, do not insert terminating resistor to the external
device. If terminating resistor can not be removed, use COM2 on the HG2G-5F, HG3G/4G instead of COM1.
- Touch has no pin number corresponding to TERM. When a termination resistor is necessary, insert one with suitable resis-
tance value between pin 8 (RDA) and pin 9 (RDB).