Compatible PLCs
If your existing project is using "SLC500" with Ver.2.30 or earlier, "SLC500 (Half Duplex)" will appear to the Protocol set-
ting with Ver.2.40 or later. SLC 500 (Half Duplex) driver is merged into the MicroLogix1200 (Full Duplex) driver.
WindO/I-NV2 software still provides the SLC 500 (Half Duplex) driver for the existing projects, but it's recommended to
use the MicroLogix1200 (Full Duplex) driver if you create a new project.
Some address format between MicroLogix 1200 (Full Duplex) and SLC 500 (Half Duplex) are slight different.
Series Name
System (CPU unit)
Link unit
WindO/I-NV2 Settings
Interface
Flow Control
Host I/F Driver
PLC-5
All PLC-5
models
that can be connected
to 1770-KF2
1770-KF2
RS232C
Connection Diagram 2
(refer to P171)
Hardware
PLC-5
RS422/485 4-wire
Connection Diagram 3
(refer to P173)
All PLC-5
models
Not required
(connects to CPU unit)
RS232C
Connection Diagram2
(refer to P171)
RS422/485 4-wire
Connection Diagram 4
(refer to P176)
SLC 500
SLC5/03
SLC5/04,
SLC5/05
Not required
(connects to CPU unit)
RS232C
Connection Diagram 1
(refer to P169)
MicroL
ogix/
SLC500
Full
Duplex)
SLC5
00
(Half
Duple
x)
Micro-Logix
MicroLogix1000,
MicroLogix1200
*1
*1. We tested with the PLC of these parts.
Not required
(connects to CPU unit)
RS232C
Connection Diagram 5
(refer to P179)
MicroLogix1100
Not required
(connects to CPU unit)
RS232C
Connection Diagram 8
(refer to P185)
-
MicroLogix1500
Not required
(connects to Mini Din
connector on CPU unit)
RS232C
Connection Diagram 5
(refer to P179)
Not required
(connects to D-sub
connector on CPU unit)
RS232C
Connection Diagram 6
(refer to P181)