External device setup manual – IDEC High Performance Series User Manual
Page 402
Chapter 2
384
External Device Setup Manual
13.4.2
Connecting with the MP2000 series via Ethernet
1. MICRO/I settings
2. PLC Settings
Item
Setting
IP Address (MICRO/I)
Set the IP address of MICRO/I in Communication Interface tab.
Subnet Mask
Set the subnet mask of MICRO/I in Communication Interface tab.
Default Gateway
Set the default gateway of MICRO/I in Communication Interface tab.
IP Address (PLC)
Set the IP address of PLC in Host I/F Network tab.
Port Number (PLC)
Set the port number of PLC in Host I/F Network tab.
The default is 10001.
Item
Setting
Transmission Parameters
IP Address
Set the IP address of PLC.
Subnet Mask
Set the subnet mask of PLC.
Default Gateway
Set the default gateway of PLC.
Connection Parameters
Local Port
Set the port number of PLC.
Node IP Address
Set the IP address of MICRO/I.
*1
*1. If the "Node IP Address" is set to "0.0.0.0", the connection is set in the "Unpassive Open mode". Any nodes in the network can access to the
controller.
Node Port
Set the port number of MICRO/I.
*2
*2. To set the connection mode to "Unpassive Open mode", set 0 to "Node Port".
Connect Type
Set the TCP.
Protocol Type
Select "Extended MEMOBUS" protocol.
Code
Set the BIN.
Please set up the head register by the side of the PLC as follows. Moreover, please give offset of each register as 0.
Module detailed setup
“Setup of a slave I/F register” “Head REG”
“reading of an Inputs Status” IW0000
“reading of an Inputs Registers” IW0000
“reading/writing” of a Coil MW00000
“reading/writing” of a Holding Registers MW00000