External device setup manual – IDEC High Performance Series User Manual
Page 207
189
4 Allen-Bradley
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Con
nection
to a PLC
External Device Setup Manual
4.4.3
PLC-5
Item
Setting
Interface
*1
*2
*1. When using the 1770-KF2 Module, select this setting using the 1770-KF2 Module DIP switch.
*2. In the case of a direct connection to the PLC-5 Processor Module, select this setting using the PLC-5 Processor Module DIP switch.
RS232C, RS485 4-wire
Baud Rate (bps)
*3*4
*3. When using the 1770-KF2 Module, select this setting using the DIP switch on 1770-KF2 Module. In case of a direct connection to the PLC-5
Processor Module, select using the 6200 Programming Software (Channel 0 configuration).
*4. The setting for this item must match the setting on the MICRO/I Series unit.
1200, 2400, 4800, 9600 or 19200
Data Bits
8 (fixed)
None or Even
Stop Bits
1 (fixed)
Half
duplex
*5
*5. Be certain to select as indicated.
Channel 0 Protocol
Duplicate Detect
Error Detect
Control Line
handshaking
Data highway plus
PLC-5 Processor Station Address
*6
*6. This setting is required regardless of whether 1770-KF2 Module is used or not. When using the 1770-KF2 Module, select this setting using the
DIP switch on PLC-5 Processor, and in the case of a direct connection to the PLC-5 Processor Module, select using the 6200 Programming
Software (Channel 0 configuration).
00 to 77 (Octal)
1770-KF2 Node Number
*7
*7. This selection is only necessary if you are using the Interface Module.
00 to 77 (Octal)
Setting the Station Address using WindO/I-NV2.
- When using the 1770-KF2 Module, select “Use 1770-KF2” checkbox in the WindO/I-NV2 Configuration - System
Setup - Project - Host I/F Driver, and set “Station Address (1770-KF2)” and “Station Address (PLC5)”.
- In case of direct connection to PLC5 Processor Module, do not select the “Use 1770-KF2” checkbox. Instead select “Sta-
tion Address (1770-KF2)”.
These numbers are to be set using octal for the PLC-5 and 1770-KF2, but hexadecimal for the WindO/I-NV2.