18.4.4
MICREX-SX series (connecting to the CPU unit loader connection connector or using the In-
terface Module.)
18.4.5
MICREX-SX series (connecting to the Ethernet port or using the Ethernet module.)
1. MICRO/I settings
2. PLC Settings
Items
Details
Interface
RS232C, RS485
Baud Rate (bps)
Use the same
settings as for the MICRO/I.
38400
Data Bits
8
Stop Bits
1
Parity
Even
Flow Control
None
- The communication settings are fixed.
- When you connect to the Interface Module,set the RS232C or RS485 operation mode as loader setting.
Set up the mode switch of Interface Module as below.
RS232C: Mode switch is No.1.or No.3
RS485:Mode switch is No.2.or No.3.
Item
Setting
IP Address (MICRO/I)
Set the IP address of MICRO/I in Communication Interface tab.
Subnet Mask
Set the subnet mask of MICRO/I in Communication Interface tab.
Default Gateway
Set the default gateway of MICRO/I in Communication Interface tab.
IP Address (PLC)
Set the IP address of PLC in Host I/F Network tab.
Port Number (PLC)
Set the port number of PLC in Host I/F Network tab.
The default is 507.
Item
Setting
IP Address
Set the IP address of PLC.
Subnet mask
Set the subnet mask of PLC .
Default Gateway
Set the default gateway of PLC.