External device setup manual – IDEC High Performance Series User Manual
Page 208
Chapter 2
190
External Device Setup Manual
4.4.4
Ethernet/IP (ControlLogix, CompactLogix, PLC-5, SLC 500, MicroLogix)
4.4.5
ControlLogix, CompactLogix, FlexLogix
Communication Interface Setting (Ethernet)
Item
Setting
Interface
Ethernet
IP Address
Set the IP address of MICRO/I.
Subnet Mask
Set the subnet mask of MICRO/I.
Default Gateway
Set the default gateway of MICRO/I.
Host I/F Network Setting
Set some network information of PLCs. It can be set to maximum of 16.
Item
Setting
Station No.
The number to select PLC when set device address.
IP Address
Set the IP address of communicated PLC.
Port Number
Set the port number of communicated PLC.
Product
Set the product of communicated PLC.
(For ControlLogix or CompactLogix, select «Logix».)
Slot Number
Set the CPU slot number of communicated PLC.
Item
Setting
Baud Rate (bps)
*1
*1. The setting for this item must match the setting on the MICRO/I Series unit.
1200, 2400, 4800, 9600 or 19200
Data Bits
8 (fixed)
Parity
None or Even
1
Flow Control
None
Serial Interface
RS232C
Protocol
DF1 Point to Point
*2
*2. Be certain to select as indicated.
Control Line
No Handshaking
Error Detection
BCC or CRC
Embedded Response
Auto Detect
Duplicate Packet Detect
Enable
Station Address
*3
*3.Select the MICRO/I Node Address using the Station Address (MICRO/I) under Configuration - System Setup - Project -
Host I/F Driver in WindO/I-NV2.
0 to 254 (decimal)