External device setup manual – IDEC High Performance Series User Manual
Page 274

Chapter 2
256
External Device Setup Manual
6.4.3
KV-700/1000/3000/5000 + KV-L20R
6.4.4
Environment settings for connection to the KV-5000/KV-LE20A/KV-LE20V
1. MICRO/I settings
2. PLC Settings
Refer to the PLC manual for details.
Item
Setting
Interface
RS232C, RS422/485 2-wire, RS422/485 4-wire
Baud Rate (bps)
1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200
Data Bits
8
Parity
Even
Stop Bits
1
-
See the operation manual of the PLC for more information.
-
When you communicate with the communication unit for the KV-L20R, uncheck the “Connect CPU Unit (Enable)/ Link Unit (Disable)”
check box for the communication setting.
Item
Setting
IP Address
Set the IP address of MICRO/I.
Subnet mask
Set the subnet mask of MICRO/I.
Default Gateway
Set the default gateway of MICRO/I.
Item
Setting
IP Address
Set the IP address of PLC.
PORT
Set the port number of PLC to communicate with MICRO/I.
Protocol
TCP/IP, UDP/IP
Item
Setting
IP Address
Set the IP address to PLC.
PORT
Set the arbitrary port number.