5 event transmission, Event transmission, External device setup manual – IDEC High Performance Series User Manual
Page 604
Chapter 4
586
External Device Setup Manual
7.5
Event Transmission
This is used to perform Event Transmission when a value in the MICRO/I or Touch data memory is changed
7.5.1
Command
Format
7.5.2
Event Data Transmission Sequence
Detailed description
Command
Code
Description
Bytes
STX
02h
Command start
1
E
45h
Event Transmission command
1
DM Address
Event Transmission address. This is expressed as the ASCII code of the hexadeci-
mal value of the address.
4
Words
Event Transmission words. The hexadecimal value expressed using ASCII code.
2
Data
DM Address data.
The hexadecimal value expressed using ASCII code.
4
ETX
03h
Only required when “with BCC” is set.
Command end of the event transmission data.
1
BCC
Only required when 'with BCC' is set.
Exclusive OR (HEX) from ENQ to before BCC converted to ASCII code.
2
CR
0Dh
End
1
- Number of Event Transmission words should not be larger than the number of Max Event Transmission Words. If Max
Event Transmission Words is 0, then Event Transmission words is set to 1.
- The Max Event Transmission Words setting is set from 0 to 255.