Pulse count methods – Yaskawa MP920 Motion Module User Manual
Page 419

10 CNTR-01 Module Specifications and Handling
10.2.3 Setting I/O Data
10-18
Pulse Count Methods
The following pulse count methods can be selected using fixed parameter 05 (Pulse Count).
* 1. Pulse Count Method
Table 10.2 Pulse Count Methods
Count Type
Pulse Count Method
*1
Multiplication
*2
Pulse C Function
Reversible
Counter
Sign mode
× 1
Stops the counter while pulse
C is being input.
Note: Fixed parameter 11 can
be used to enable or
disable the counter.
× 2
A/B mode
× 1
× 2
× 4
Up/Down mode
× 1
× 2
Interval
Counter
Sign mode
× 1
Latches the count result and
resets the counter at the rising
edge of pulse C.
× 2
A/B mode
× 1
× 2
× 4
Up/Down mode
× 1
× 2
Frequency
Measurement
Sign mode
× 1
Pulse C is not used
(or pulse C is invalid).
× 2
A/B mode
× 1
× 2
× 4
Up/Down mode
× 1
× 2
• Sign Mode
Positive Logic 5-V Differential Input:
Increments the count if pulse A is input when pulse B is at low level.
(Positive for frequency measurements.)
Decrements the count if pulse A is input when pulse B is at high level.
(Negative for frequency measurements.)
Negative Logic 5-V Differential Input:
Decrements the count if pulse A is input when pulse B is at high level.
(Positive for frequency measurements.)
Increments the count if pulse A is input when pulse B is at low level.
(Negative for frequency measurements.)
Positive Logic 12-V Pull-up Collector Input:
Decrements the count if pulse A is input when pulse B is at high level.
(Positive for frequency measurements.)
Increments the count if pulse A is input when pulse B is at low level.
(Negative for frequency measurements.)