Yaskawa MP920 Motion Module User Manual
Page 126

4 Parameters
4.2.1 Motion Fixed Parameters
4-6
7
Rated Motor Speed
Setting
(NR)
1 to 32000
(Default = 3000)
1 = 1 min
-1
√
√
√
√
8
Number of Feed-
back Pulses Per
Rotation
(FBppr)
Multiple of 4
between 4 and
65532
(Default = 2048)
1 = 1 pulse/rev
Set the value prior to
multiplying.
√
√
√
−
9
D/A Output
Voltage at 100%
Speed (V1)
0.001 to 10.000
(Default = 6 V =
6.000)
1 = 1 V
√
√
−
−
Number of Feed-
back Pulses Per
Rotation (For high-
resolution)
(Default = 2048)
1 = 1 pulse/rev
Set the value prior to
multiplying.
−
−
√
−
10
D/A Output
Voltage at 100%
Torque Limit
(V2)
0.001 to 10.000
(Default = 3 V =
3.000)
1 = 1 V
Valid only for the SVA (2
axes) Module.
−
√
−
−
11
Input Voltage at
100% Speed
Monitoring (A/D)
(MV1)
0.001 to 10.000
(Default = 6 V =
6.000)
1 = 1 V
Valid only for the SVA (2
axes) Module.
−
√
−
−
12
Not used.
−
−
−
−
−
−
13
DI Latch Signal
Selection
(DIINTSEL)
0 or 1
(Default = 0)
0: DI input signal
1: Pulse-C input signal
√
√
−
−
14
Additional Func-
tion Selections
(AFUNCSEL)
Bits 0 to 1:
Not used.
−
−
−
−
−
Bit 2: LIMITSEL
Limit Switch Signal Selection
0: Use OB01F.
1: Use the DI signal.
√
−
−
√
Bit 3: LMT_LSEL Reverse Limit Signal Selection
for Zero Point Return
0: Use OB21C.
1: Use the DI signal.
−
−
−
√
Bit 4: LMT_RSEL Forward Limit Signal Selection
for Zero Point Return
0: Use OB21D.
1: Use the DI signal.
−
−
−
√
Bit 5: EMGSEL
Emergency Stop (DI) Signal
Selection
0: Emergency stop
(hard)
1: Deceleration stop
(soft)
−
−
−
√
Bit 6: ABSRDSEL Absolute Position Read at
Startup
0: Execute.
1: Do not execute.
√
√
−
−
Bit 7: MCMDSEL Motion Command Code
Selection
0: Not used.
1: Use.
√
√
−
√
Bit 9
Σ-II Series SERVOPACK
Selection
0: OFF
1: ON
√
√
−
−
Bits 12 to 15
Error Count Alarm Detection
Setting Coefficient
Setting range: 0 to 4
√
√
−
−
Table 4.2 Motion Fixed Parameters (cont’d)
No.
Name
Setting Range/
Bit Name
Meaning
Remarks
SVA
-01A
SVA
-02
A
SVB
-01
PO-
01