6.2 SVB-01 Parameters
6-33
6
35
Rapid Traverse
Speed (RV)
OL22
0 to 2
31
-1
Set the rapid traverse speed in 10
n
reference units/min (n:
Number of digits below decimal point) if OB01D:
Speed Reference Selection is set to “0.”
Other setting units are expressed as follows:
Pulse unit: 1 = 1000 pulses/min
mm unit: 1 = 1 mm/min
deg unit: 1 = 1 deg/min
Inch unit: 1 = 1 inch/min
3000
37
External Posi-
tioning Travel
Distance
(EXMDIST)
OL24
-2
31
to 2
31
-1
Set the distance the axis moves from the time a latch sig-
nal (external positioning signal) is input until the axis
comes to a stop when Motion Command Code
(OW20) is set to 2 (External Positioning).
Use the same unit as for the SERVOPACK.
0
39
Stopping
Distance
(STOPDIST)
OL26
-2
31
to 2
31
-1
This parameter is used by the system. Do not use it.
0
41
Step Travel
Distance
(STEP)
OL28
0 to 2
31
-1
Set the travel distance in reference units for Step execu-
tion for the OW20: Motion Command Code.
• Unit: Reference unit
0
43 to
44
Not used.
OL2A
−
Set to “0.”
0
45
Override (OV)
OW2C
0 to 32767
Set the override for the output speed as a percentage of
the OL22: Rapid Traverse Speed in 0.01% units.
For interpolation related commands, set override in the
register specified in the Group Definition Window.
Rapid Traverse Speed Output:
Rapid Traverse Speed
×
Override = Output speed
(OL22) (OW2C)
100.0
This parameter is valid when fixed parameter No. 17: Override Selec-
tion (bit 9 of Motion Controller Function Selection Flags) is set to
Enabled.
Table 6.3 Motion Setting Parameters (cont’d)
No.
Name
Register
Number
Setting Range/
Bit Name
Description
Factory
Setting
Rapid Traverse
Speed
(OL
22)
Override
(OW
2C)
Fixed parameter
b9: Override
Selection
100%
Enabled
Output
speed
Disabled