6.2 SVB-01 Parameters

6-33

6

35

Rapid Traverse
Speed (RV)

OL††22

0 to 2

31

-1

Set the rapid traverse speed in 10

n

reference units/min (n:

Number of digits below decimal point) if OB††01D:
Speed Reference Selection is set to “0.”
Other setting units are expressed as follows:
Pulse unit: 1 = 1000 pulses/min
mm unit: 1 = 1 mm/min
deg unit: 1 = 1 deg/min
Inch unit: 1 = 1 inch/min

3000

37

External Posi-
tioning Travel
Distance
(EXMDIST)

OL††24

-2

31

to 2

31

-1

Set the distance the axis moves from the time a latch sig-
nal (external positioning signal) is input until the axis
comes to a stop when Motion Command Code
(OW††20) is set to 2 (External Positioning).
Use the same unit as for the SERVOPACK.

0

39

Stopping
Distance
(STOPDIST)

OL††26

-2

31

to 2

31

-1

This parameter is used by the system. Do not use it.

0

41

Step Travel
Distance
(STEP)

OL††28

0 to 2

31

-1

Set the travel distance in reference units for Step execu-
tion for the OW††20: Motion Command Code.

• Unit: Reference unit

0

43 to

44

Not used.

OL††2A

Set to “0.”

0

45

Override (OV)

OW††2C

0 to 32767

Set the override for the output speed as a percentage of
the OL††22: Rapid Traverse Speed in 0.01% units.
For interpolation related commands, set override in the
register specified in the Group Definition Window.
Rapid Traverse Speed Output:
Rapid Traverse Speed

×

Override = Output speed

(OL††22) (OW††2C)

100.0

This parameter is valid when fixed parameter No. 17: Override Selec-
tion (bit 9 of Motion Controller Function Selection Flags) is set to
Enabled.

Table 6.3 Motion Setting Parameters (cont’d)

No.

Name

Register

Number

Setting Range/

Bit Name

Description

Factory

Setting

Rapid Traverse

Speed

(OL

22)

Override

(OW

2C)

Fixed parameter

b9: Override

Selection

100%

Enabled

Output

speed

Disabled