2 alarms and actions taken, 1 alarm il**22, 1 alarm il22 – Yaskawa MP920 Motion Module User Manual
Page 362

8 Troubleshooting
8.2.1 Alarm IL22
8-6
8.2
Alarms and Actions Taken
This section describes individual alarms and the actions that should be taken.
8.2.1
Alarm IL22
This section describes the axis alarm flag (IL22).
Alarm data will be reported at IL22 if a motion command is used in Position Control
Mode. Some alarm will not occur for certain Motion Modules. Refer to the following table
for applicability.
Note: Yes: Supported, No: Not supported
IL22
Alarm
SVA-
01A
SVA-
02A
SVB-01
PO-01
Bit 0
SERVOPACK Error
No
No
Yes
No
Bit 1
Positive Overtravel
Yes
Yes
Yes
No
Bit 2
Negative Overtravel
Yes
Yes
Yes
No
Bit 3
Positive Software Limit
Yes
Yes
Yes
Yes
Bit 4
Negative Software Limit
Yes
Yes
Yes
Yes
Bit 5
Servo OFF (Excitation ON)
No
No
Yes
Yes
Bit 6
Positioning Time Over
Yes
Yes
Yes
No
Bit 7
Positioning Travel Distance Exceeded
(Speed Exceeded)
No
No
Yes
Yes
Bit 8
Filter Type Change Error
No
No
Yes
No
Bit 9
Filter Time Constant Change Error
No
No
Yes
No
Bit 10
Control Mode Error
Yes
Yes
Yes
Yes
Bit 11
Zero Point Not Set
Yes
Yes
Yes
No
Bit 12
Not used.
−
−
−
−
Bit 13
Not used.
−
−
−
−
Bit 14
Servo Drive Synchronous Communica-
tions Error
No
No
Yes
No
Bit 15
Servo Drive Communications Error
No
No
Yes
No
Bit 16
Servo Drive Command Timeout Error
No
No
Yes
No
Bit 17
Absolute Encoder Count Exceeded
Yes
Yes
Yes
No
Bit 18
Broken PG Wiring
Yes
Yes
No
No