Slaved Zone Damper Wiring
For large zones, it may be necessary to have more than one air damper 
controlled by a VAV/Zone Controller Actuator Package and its associ-
ated space sensor. The WCC III system allows for connecting up to 
two additional slaved zone dampers to the master VAV/Zone Controller 
Actuator Package. Slaving is not available for pressure independent 
damper applications. 
Note:
Each slaved actuator is rated at 6 VA each. This 6 VA
load must be included in the transformer sizing and 
branch circuit calculations for the Power/Comm board. 
See the previous section regarding transformer sizing of 
the Power/Comm board for complete information.
Two Slave Wiring Adapters ( OE267) consisting of a slave wiring 
interface card and modular cable are supplied with the OE523 Round 
Slaved Zone Damper, OE738 Slaved VAV/Zone Rectangular Damper 
Kit, and the OE282-03 Slaved VAV/Zone Damper Kit. These are required 
when attaching slave actuator(s) to the master zone damper. One slave 
wiring interface card should be mounted near the control enclosure of 
the master VAV/Zone Controller Actuator Package. It is mounted by 
fastening the plastic snap-track to suitable sheet metal mounting surface 
with the sheet metal screws provided. The other card is mounted in the 
control enclosure of the slaved zone damper. Run 24 AWG minimum 
wire between the slave wiring interface cards. Connect modular cables 
to the slave wiring interface cards and to the zone actuators as shown. 
See Figure 14 for complete wiring details.
Figure 14: Slaved Zone Damper Wiring & Connection Diagram
Slaved Zone Damper Wiring
16
VAV/Zone Controller Actuator Package Technical Guide
Installation & Wiring