beautypg.com

General instructions, Alarms – WattMaster WM-WCC3-TGD-01B User Manual

Page 65

background image

1. GENERAL INSTRUCTIONS

WCC III Technical Guide

1-11

Satellite #1

ANALOG INPUT #1

Description: RM 101

Type: Analog

Pattern for values associated with this input: xxx.x

Units @ 0% scale: 0.0 Deg F Units of Measure Message #: 1

@ full scale: 100.0 Deg F Filter Time Constant: 8 seconds

-------------------ALARMS--------------------

Controlled by: W1

Limits

Low

High

Alarm

Type:

1

On

68.0

80.0

Deg

F

Alarm Message #’s: Low 2 High 1

Off

50.0 90.0 Deg F

Alternate Limits selected by:....

On (alt)

0.0

0.0 Deg F

Off (alt)

0.0

0.0 Deg F

Limit overlap time

after control change: 20 Minutes

Local set

55.0 90.0 Deg F

----------------------BINARY SETPOINT-----------------------

OFF

Above

0.0

Deg

F

On

Message

#:

0

OFF

Below

0.0

Deg

F

Off

Message

#:

0

HOME for menu

Alarm Call-Out

The WCC III will automatically e-mail a report of the alarms to
an e-mail address. There are eight different alarm types or alarm
priorities. The fi rst fi ve alarm types can “e-mail-out”; each of these
fi ve alarm types can e-mail 3 separate e-mail addresses.

Analog Alarm Limit

Each analog input can have a low and high limit assigned to it
on the Analog Input Screen. If the value of the analog input falls
below the low limit or rises above the high limit, the system
automatically generates an alarm. For example, assume that the
analog input in question is a room temperature sensor located in
an offi ce space. If the space temperature falls below 68 °F or rises
above 80 °F during the occupied period, we want an alarm to call
out. To set up the alarm limits, fi rst sign on by accessing the System
Parameter Screen
and entering your password. An access level of
1 or greater is required to enter or change alarm limits. After you

are signed on, return to the Main Menu and place the cursor over
“ANALOG INPUT” and press

. An Analog Input Screen

similar to what is shown below should come into view:

The alarm limits along with the alarm type and alarm message
numbers are assigned on this screen (see the Analog Input Screen
in Section 3 for more information). If the space temperature drifts
out of the entered alarm limits, the system will automatically
generate an alarm. For example, assume that the space temperature
rises above the high limit value of 80 °F. Alarm message #1 (High
Temperature) along with the time and date of the alarm and the
high peak value of the room temperature will appear on Analog
Input Summary Screen
and the Alarm Summary Screen. Within
one minute from the time the alarm appears on the screen, it
will automatically be e-mailed if enabled. (To acknowledge
alarms, select

from the Top Menu Bar and then select

or

described

in the Help Screen, Analog Input Summary Screen, and Alarm
Summary Screen
in Section 3 of this guide.

Alarms

This manual is related to the following products: