General instructions, Alarms – WattMaster WM-WCC3-TGD-01B User Manual
Page 65
1. GENERAL INSTRUCTIONS
WCC III Technical Guide
1-11
Satellite #1
ANALOG INPUT #1
Description: RM 101
Type: Analog
Pattern for values associated with this input: xxx.x
Units @ 0% scale: 0.0 Deg F Units of Measure Message #: 1
@ full scale: 100.0 Deg F Filter Time Constant: 8 seconds
-------------------ALARMS--------------------
Controlled by: W1
Limits
Low
High
Alarm
Type:
1
On
68.0
80.0
Deg
F
Alarm Message #’s: Low 2 High 1
Off
50.0 90.0 Deg F
Alternate Limits selected by:....
On (alt)
0.0
0.0 Deg F
Off (alt)
0.0
0.0 Deg F
Limit overlap time
after control change: 20 Minutes
Local set
55.0 90.0 Deg F
----------------------BINARY SETPOINT-----------------------
OFF
Above
0.0
Deg
F
On
Message
#:
0
OFF
Below
0.0
Deg
F
Off
Message
#:
0
HOME for menu
Alarm Call-Out
The WCC III will automatically e-mail a report of the alarms to
an e-mail address. There are eight different alarm types or alarm
priorities. The fi rst fi ve alarm types can “e-mail-out”; each of these
fi ve alarm types can e-mail 3 separate e-mail addresses.
Analog Alarm Limit
Each analog input can have a low and high limit assigned to it
on the Analog Input Screen. If the value of the analog input falls
below the low limit or rises above the high limit, the system
automatically generates an alarm. For example, assume that the
analog input in question is a room temperature sensor located in
an offi ce space. If the space temperature falls below 68 °F or rises
above 80 °F during the occupied period, we want an alarm to call
out. To set up the alarm limits, fi rst sign on by accessing the System
Parameter Screen and entering your password. An access level of
1 or greater is required to enter or change alarm limits. After you
are signed on, return to the Main Menu and place the cursor over
“ANALOG INPUT” and press
. An Analog Input Screen
similar to what is shown below should come into view:
The alarm limits along with the alarm type and alarm message
numbers are assigned on this screen (see the Analog Input Screen
in Section 3 for more information). If the space temperature drifts
out of the entered alarm limits, the system will automatically
generate an alarm. For example, assume that the space temperature
rises above the high limit value of 80 °F. Alarm message #1 (High
Temperature) along with the time and date of the alarm and the
high peak value of the room temperature will appear on Analog
Input Summary Screen and the Alarm Summary Screen. Within
one minute from the time the alarm appears on the screen, it
will automatically be e-mailed if enabled. (To acknowledge
alarms, select
from the Top Menu Bar and then select
or
described
in the Help Screen, Analog Input Summary Screen, and Alarm
Summary Screen in Section 3 of this guide.
Alarms