10. RS-485 COMMUNICATIONS
WCC III Technical Guide
10-8
Lightning Suppression
Lightning Suppression
Lightning is an act of nature and as such cannot be predicted or 
controlled. There is NOTHING that will COMPLETELY protect 
any electronic equipment from the massive effects of a direct or 
near hit from lightning. WattMaster Controls has taken a number 
of steps to protect the electronic components and the incoming 
pathways of its equipment from voltage surges that may enter 
them. These incoming pathways are defi ned as: 24VAC power, 
RS-232 data communications, RS-485 data communications, input 
wiring, and relay control circuits. All of these pathways have been 
protected using a variety of devices, including varistors, diodes, 
transorbs, and excessive ground planes on all of our circuit boards. 
There are several “General Rules” that can be applied towards 
lightning protection:
General Rule Number One:
Any time the WCC III /Satellite
RS-485 communication’s loop enters or leaves a building, there 
needs to be a properly installed and grounded lightning protection 
device or lightning suppressor device.
General Rule Number Two:
No lightning protection devices
or lightning suppressor devices will protect against a direct 
lightning hit. 
General Rule Number Three:
For a lightning protection
device or lightning suppressor device to work properly, there needs 
to be an actual earth-ground connection point as near as possible 
to the lightning protection device or lightning suppressor device. 
Being feet away from the actual earth-ground connection does not 
work, Being inches away is always the best possible connection 
point for this actual ground connection.
At some point you have to ask the question: “What
exactly are you trying to protect?”
Lightning could enter the building via an analog input on a TUC-2R, 
and then it could cause problems with the RS-485 communications 
loop on the SAT 3C/D/F TUC communications loop along with 
more problems on the SAT RS-485 communications loop. You 
could have your entire building’s control system go down due to a 
close lightning strike. The most likely path that lightning would take 
to do the most damage would be on the RS-485 communications 
loop that connects the Satellite controllers to each other. You may 
decide to put multiple lightning protection devices or lightning 
suppressor devices on every RS-485 communications loop as a 
preventive safety measure.
WattMaster Controls sells an RS-485 communications loop 
lightning protection device. The WattMaster part number is 
OE437-03. 