Wcc3.exe screen descriptions, Analog input thermistor+ screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 158
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-44
Analog Input Thermistor+ Screen
Satellite # 1
ANALOG INPUT # 2
Description: Room
Type: Analog Thermistor+
Pattern for values associated with this input: xxx.x
Degree Type: ºF
Units of Measure message #: 1
Offset: 0.0 Deg F
Filter time constant: 0 seconds
b0: 0.0014062
b1: 0.00023671
b3: 0.0000001023
__________________ ALARMS _____________________
Controlled
by:
0
Limits
Low
High
Alarm Type: 1
On
40.0 60.0 Deg F
Alarm Message #’s: Low 1 High 2
Off
40.0 60.0 Deg F
Alternate limits selected by: 0
On (alt)
40.0 60.0 Deg F
Off (alt)
40.0 60.0 Deg F
Limit overlap time
after control change: 0 Seconds
Local set
40.0 60.0 Deg F
================= BINARY SETPOINT ===================
OFF Above
8.0 Deg F
On Message #: 5 Flow
OFF Below
5.0 Deg F
Off Message #: 6 No Flow
HOME for menu
ANALOG INPUT THERMISTOR+ SCREEN
Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8
Satellite # _______
Specifi es the number of the satellite which you are currently
editing. If you would like to edit a different satellite, use the arrow
keys to move the cursor to this fi eld, type in the desired satellite
number, and press
.
Analog Input # ________
This “fi eld” actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT> You may make your selection by pressing the until the desired choice appears and then pressing . (If you select a point type that is different than that currently being displayed, the Additionally, this fi eld specifi es the point number to edit. For the . Description: A short message is entered here which is displayed on Summary Type: Analog Thermistor+ This fi eld is automatically fi lled in by the system. On screens 2-8,
screen will be rewritten with the appropriate screen and data.)
Analog Input Screen, this number can range from one to eight,
corresponding from A1 to A8, respectively. If you would like to
edit a different point, move the cursor to this fi eld by using the
arrow keys, enter the desired point number, and press
Screens to help you remember points within the system. You
may enter up to ten characters (control codes, ALT codes, and the
double quote character are not allowed).
this will always read “ANALOG.” On screen number 1, it will
read either “ANALOG” or “PULSE” depending on the position
of the pulse switch on the satellite controller.