Sat 3p installation guide, Analog input screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 743

18. SAT 3P INSTALLATION GUIDE
WCC III Technical Guide
18-9
Alternate Limits Selected By:
Specifi es the point that initiates the Alternate mode. When this 
address is zero (or OFF), the Normal alarm limits are selected; 
when it is one (or ON), the Alternate alarm limits are selected.
Limits
Low High
On
_____ _____ °. F
Off
_____ _____ °. F
On (alt)
_____ _____ °. F
Off (alt)
_____ _____ °. F
Local Set
_____ _____ °. F
This group of inputs specifi es the alarm limits for the “Normal,” 
“Alternate,” and “Local Set” modes. Each mode has a LOW and 
HIGH limit. When the value of the analog input goes out of these 
limits, an alarm is generated, and the alarm will automatically 
display and e-mail out.
There are two fi elds on this screen that determine which set of 
limits are active—the status of the “Controlled by” fi eld and the 
status of the “Alternate Limits selected by” fi eld. When the value 
that has been input in the “Controlled by” fi eld is ON, either the 
“On” limits or the “On (Alt)” limits are active depending on the 
status of the value input in the “Alternate Limits selected by” fi eld. 
If the value in the “Alternate” fi eld is On, the “On (Alt)” limits are 
used, and when the “Alternate” value is OFF, the “On” limits are 
used.
 Alternate Limits Active Alarm
Controlled by: Selected by: Limits:
On Off
On
On On
On (Alt)
Off Off
Off
Off On
Off (Alt)
The local set alarm limits become active if the MCD quits 
communicating with the satellite controller. After communications 
are re-established, any alarms that occurred while the satellite was 
in local set will be reported.
Limit overlap time after control change:
This specifi es the amount of time the WCC software will wait after 
a control change (i.e., on/off schedule, alternate mode, local set 
mode) before deciding to generate an alarm. The fi rst input is a 
user-entered number from 1 to 60, and the second input is either 
seconds or minutes. This second input is a “choice” fi eld; the list of 
available choices will be displayed at the bottom of the screen:
You may make your selection by pressing the
until
the desired choice is selected and then pressing
.
------ BINARY SETPOINTS ------
____Above:____
____Below:____
These inputs are used to convert the analog signal to a binary (On/
Off) signal. The value that is going ON and OFF is a software point 
referred to as a comparator. Each analog input has a comparator 
associated with it named “Cn.” The comparator for analog input #1 
is “C1,” analog input number 2 is “C2,” and so on. The status of the 
comparator can be seen on the Analog Input Summary Screen.
When the 
user has 
selected:
The value of the comparator is:
OFF Above & 
OFF Below:
OFF when the Analog Input value is greater than the 
ABOVE setpoint or less than the BELOW setpoint, 
and ON when the Analog Input value is equal to 
either one or between the two setpoints.
OFF Above & 
ON Below:
OFF when the Analog Input value is greater than 
or equal to the ABOVE setpoint or until the Analog 
Input value becomes less than the BELOW setpoint, 
and ON when the Analog Input value is less than or 
equal to BELOW setpoint or until the Analog Input 
value becomes greater than the ABOVE setpoint. 
ON Above & 
OFF Below:
OFF when the Analog Input value is less than or 
equal to the BELOW setpoint or until the Analog 
Input value becomes greater than the ABOVE 
setpoint, and ON when the Analog Input value is 
greater than or equal to the ABOVE setpoint or 
until the Analog Input value becomes less than the 
BELOW setpoint.
ON Above & 
ON Below:
OFF when the Analog input value is equal to either 
one or between the two setpoints, and ON when 
the Analog Input value is greater than the ABOVE 
setpoint or less than the BELOW setpoint.
Because this is a “choice” fi eld, a list of available choices will be 
displayed at the bottom of the screen:
You may make your selection by pressing the
until
the desired choice is selected and then pressing
.
On Message #:
Off Message #:
Specifi es a pair of message numbers, the fi rst for the ON state and 
the second for the OFF state of the comparator. These numbers 
are used by the system to reference a message on the ON/OFF 
Units Message Screen. For example, the comparator might be set 
up to come on when the outside air temperature is below 55 °F for 
economizer operation. Set up the On/Off Message Screen so that 
message #3 is “ECON” and message #4 is “REFRIG.” The “On 
Message” number would be “3” (ECON), and the “OFF Message” 
number would be “4” (REFRIG).
Analog Input Screen
