WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-60
Description: _____________
A short message is entered here which will be displayed on Summary 
and Data Entry/Editing Screens to aid you in remembering points 
within the system. You may enter up to ten characters (control 
codes, ALT codes, and the double quote character are not allowed).
Contact Open Message #: ____
Contact Closed Message #: ____
Specifi es a pair of message numbers, the fi rst for the contact open 
state and the second for the contact closed state. These numbers 
refer to a message on the On/Off Message Screen. For example, 
message #1 might be “Fan On” and message #2 “Fan Off.” If 
you want the message on the Control Output Summary Screen to 
be “Fan On” when the satellite contact is closed, enter “#1” as the 
contact closed message etc.
Minimum Off Time:
_____ seconds
Minimum On Time:
_____ seconds
Specifi es the minimum ON and OFF times for switching a load 
to its opposite state (i.e., ON to OFF or OFF to ON). That is, once 
the satellite contact closes it will remain closed for the minimum 
ON time, and once it opens it will remain open for the minimum 
OFF time. The range is 0 to 60 seconds or minutes, depending on 
the unit of time selected. Because this is a “choice” fi eld, the list 
of available choices will be displayed at the bottom of the screen:
Make your selection by pressing the
once for each
choice, and when the desired unit of time appears, press the
key.
Note that the minimum ON and OFF time has precedence over 
demand limiting, overrides, etc.
Contact is:
_________in “On” Schedule Selected by:________
_________in Primary Alt Mode Selected by:________
_________in Secondary Alt Mode Selected by:________
_________in Local Set Selected by:________
The fi rst fi eld specifi es whether the satellite contact is to Open or 
Close when the binary value entered in its Selected by fi eld goes 
On.
The Primary Alt mode has highest priority, followed by Secondary 
Alternate, and then On Schedule.
Since the fi rst fi eld is a “choice” fi eld, the list of available choices 
will be displayed at the bottom of the screen:
On the “On” schedule
< OPEN, CLOSED, HOLD LAST >
On the Primary Alt Mode, Secondary Alt Mode, and Local Set
Make your selection by pressing the
once for each
choice until the desired contact state has been selected, and then 
press 
.
Note that the
HOLD LAST
is available for Primary Alt,
Secondary Alt and Local Set modes only. If
HOLD LAST
is
selected in the Local Set mode, the contact will stay closed if 
it was closed at the time the satellite went into local set or will 
stay open if it was open when the satellite went into local set.
Control Output Time Clock Screen