WattMaster WM-WCC3-TGD-01B User Manual
Page 602
WCC III Technical Guide
13A-18
13. WCC III - MCD INSTALLATION GUIDE
Using the MCD-Menu Program
After you have entered in all of the required IP addresses, subnet
masks, Gateways, and/or Nameservers, the program will now
change the internal IP network confi guration fi les within the Linux
operating system of the WCC III – MCD. It will take a few seconds
to do this function, and will display the following messages:
Confi guring interface:
/sbin/ifconfi g eth0 192.168.100.100 netmask 255.255.255.0
broadcast 192.168.100.255
Deleting old interface route:
/sbin/route del -net 192.168.100.0 netmask 255.255.255.0 eth0
Setting interface route:
/sbin/route add -net 192.168.100.0 netmask 255.255.255.0
eth0
Deleting old default route:
/sbin/route del default
Setting default route:
/sbin/route add default gw 192.168.100.1
Writing /etc/network/interfaces:
Writing /etc/resolv.conf:
When completed the following information will be displayed:
New netstat settings:
192.168.100.100 0.0.0.0 255.255.255.0 U 0 0 0 eth0
192.168.200.0 0.0.0.0 255.255.255.0 U 0 0 0 eth0
0.0.0.0 192.168.100.1 0.0.0.0 UG 0 0 0 eth0
Network Confi guration Done.
**************************************************
* Exiting Program. *
**************************************************
wcciii@wcciii-mcd:~$
The mcd-menu program, as part of the setup process for the
IP connections, has on purpose exited the mcd-menu program.
This is normal operation.
Copy BackTask data Files to USB Drive (Choice #2)
This sub program will copy all of the useful WCC III data fi les to
a USB drive (User / Contractor provided), assuming that there is a
USB drive plugged into the USB port on the WCC III – MCD. It
will copy all of these fi les to the root of the USB drive.
If there is not a USB hard drive in the USB port on the front of the
WCCIII – MCD, this program assumes that there is a USB drive
there even if it is not there. It will not report that there is a drive
reading or writing error or any other errors. So when backing up,
make sure that there is a USB hard drive in the USB socket port on
the front of the WCCIII – MCD, and also there should be a LED
on this USB hard drive that should light up when data is written or
read from it. Please verify that this LED operates when backing up
data to this USB hard drive.
All WCC III jobsites have multiple specifi c custom data fi les that
are the responsibility of the end user and/or mechanical contractor.
Any loss or the retention of these jobsite specifi c custom data fi les
are not within WattMaster Controls Inc. liabilities.
The following will be displayed on the screen:
Selecting Copy BackTask Files to USB Drive.
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
AlarmBits.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
AlarmMessage.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
DutyCycleSchedule.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
EnergyConsumption.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
GeneralMessage.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
GlobalAnalog.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
GlobalBinary.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
HolidaySchedule.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
LookUpTable.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
NetworkInformation.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
OperatorCode.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
OptimalSchedule.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
OverrideSchedule.dat
Copying fi le: /home/wcciii/.wine/drive_c/Backtask/
PidProgram.dat