beautypg.com

Wcc iii technical guide 15-9 – WattMaster WM-WCC3-TGD-01B User Manual

Page 701

background image

WCC III Technical Guide

15-9

15. SAT 3C/D/F INSTALLATION

Dip Switch Settings and LEDs

24VAC & GND (POWER CONNECTIONS)

This SAT 3C/D/F controller’s power requirements are 24VAC and it draws 10 VA. Please note: You must observe polarity when connecting the

power connections to the SAT 3C/D/F controller or else damage to the SAT 3C/D/F controller could result.

.

R & T & SHIELD (SAT COMMUNICATIONS CONNECTIONS)

Communications loop can be “home run" to a power and switchable comm board - WM part # PL102224. The use of a shielded twisted pair

wire is required, such as WM part # WR-NL-WR-18 or WR-LL-WG-18. When connecting the communication wiring from satellite controllers

to other satellite controllers, you must wire "R" to "R" and "T" to "T", and "SHIELD" to SHIELD". The shield connection for all of the WCC III

type RS-485 communications loops is required for all WCC III devices, SAT III, SAT 3C/D/F, SAT 3P, TUCs, RTUs, and VAVZ II controllers.

R & T & SHIELD (TUC COMMUNICATIONS CONNECTIONS)

This RS-485 TUC communications loop can be daisy chained from one TUC/RTU type controller to the next TUC/RTU type controller or the TUC

communications loop can be "home run" to a power and switchable comm board - WM part # PL102224. The use of a shielded twisted pair wire

is required, such as WM part # WR-LL-WG-18 or WR-NL-WR-18. When connecting the TUC communication's loop wiring from the satellite

controllers (SAT 3C/D/F) to the first TUC/RTU device, you must wire "R" to "T" and "T" to "R" and "SHLD" to "SHLD". But other TUC/RTU

WCC III type RS-485 communications loops is required for all WCC III devices, SAT III, SAT 3C/D/F, SAT 3P, TUCs, RTUs, and VAVZ II controllers.

SAT 3C/D/F ADDRESS DIPSWITCH

TOP DIPSWITCH

OPTION 2 switch is not used at this time.

OPTION 1 switch is not used at this time.

LOCAL SET DISABLE switch is used to disable the SAT 3C/D/F controller's LOCSET (LOCAL SET) mode.

TEST switch is used for testing purposes.

LEDs

There are eight LEDs on the front of the SAT 3C/D/F controller.

TUC REC- Every time a communications packet is received by the SAT 3C/D/F controller this LED will blink.

TUC XMIT -

transmitted

.

Every time a communications packet is

by the SAT 3C/D/F controller this LED will blink

LOCAL SET - The local set will turn on if the SAT 3 C/D/F controller stops communicating with the WCC III - MCD.

STATUS, "C" MODE and "D" MODE- See chart listed below:

Heart Beat : Blinks for every calculation loop

SATIII

Status3 LED

SAT3C

LED "C"

SAT3D

LED "D"

SAT3F

LED "D"

Second Blink: Blinks for every second

SAT3

Status1 LED

SATC

Status LED

SATD

Status LED

SATF

Status LED

Power On Delay: Blinks for every second during power on delay

SAT3

Status2 LED

SAT3C

LED "D"

SAT3D

LED "C"

SAT3F

LED "C"

Watchdog Enable: Blinks for every 8 seconds if watchdog is enabled

SAT3

Status2 LED

SAT3C

LED "D"

SAT3D

LED "C"

SAT3D

LED "C"

SAT XMIT- Every time a communications packet is transmitted by the SAT 3C/D/F controller, this LED will blink. This communications packet originates

at the SAT 3C/D/F controller.

SAT REC - Every time a communications packet is received by the SAT 3C/D/F controller, this LED will blink. This communications packet originates

LOCAL SET switch is used to enable the SAT 3C/D/F controller’s LOCSET mode and is used when the SAT 3C/D/F controller is still communicating

at the WCC III - MCD.

BAT ON/OFF switch does nothing. It was originally intended to blank out the memory on the satellite’s CPU RAM chip and was a carry-over

from the old SAT 2 C/D controller.

Address to #20. Whenever setting this address dipswitch setting, you must cycle power up to the SAT 3C/D/F controller.

switch #3 and switch #4 ON sets the SAT 3 D/F Controller’s to #12. Another example setting with switches #3 and #5 on, sets the SAT 3 D/F controller’s

Sets the SAT 3C/D/F controller’s address to #64. Switch #8 ON sets the SAT 3 C/D/F controller’s address to #128. These 8 switches are additive, so setting

This dipswitch sets the address setting for the SAT 3 C/D/F controller. The SAT 3 D/F controller has a valid address range is from 4 to 239 in increments

of 4 starting at address #4. The SAT 3C controller has a valid address range from 8 to 239 in increments of 8 starting at address #8. The following explains

how to set the SAT 3C/D/F controller’s address: Switch #3 ON sets the SAT 3D/F controller’s address to #4. Switch #4 ON sets the SAT 3C/D/F controller’s

address to #8. Switch #5 ON, sets the SAT 3C/D/F controller’s address to #16. Switch #6 ON sets the SAT 3C/D/F controller’s address to #32. Switch #7 ON

type controllers on the TUC communications loop must be wired "R" to "R" and "T" to "T", and "SHIELD". The shield connection for all of the

The RS-485 satellite communications loop can be daisy chained from one satellite controller to the next satellite type controller or the satellite

OPTION 4 switch is not used at this time.

OPTION 3 switch is not used at this time.

This manual is related to the following products: