WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-144
Data Pattern: _____
Specifi es the number of signifi cant digits for analog global values
displayed by the system. Because this is a “choice” fi eld, the list of
available choices will be displayed at the bottom of the screen:
Make your selection by pressing the
once for each
choice until the desired default choice has been selected, and then
press
.
Units of Measure:
Specifi es a message number to be used throughout the system to
reference a textual message which is displayed with the values
associated with this global. For example, if units of measure
message #4 is Deg F, and the units of measure message for the
specifi c analog global is degrees Fahrenheit, then the units of
measure would be 4.
In Local Set this global defaults to
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:
< LAST, FIXED >
Make your selection by pressing the
once for each
choice until the desired default choice has been selected, and then
press
.
The term local set means that communication is lost between
the MCD and the satellite controllers. If the MCD stops
communicating, the global analog values will be gone. This
input allows you to specify a default value for the global
analog if the MCD quits communicating. You may input a fi xed
number, or you may choose to select LAST VALUE. If LAST
VALUE is chosen, the global analog will default to the value it
had when communications with the MCD were lost.
Map From:
Specifi es an analog point address that acts as the input signal
source for the output valve.
Extend Data to next Table
Each look up table can hold up to 60 sets of data. If you have an
application which requires a larger look up table, the data may be
extended to the next look up table.
Mode
Because this is a “choice” fi eld, the list of available choices will
be displayed at the bottom of the screen:
External, Dual Valve, Proportion, Dual Ramp, Multi-Proportion, Pulse Start> Make your selection by pressing the once for each choice until the desired mode type has been selected, and then press . One of the following screens will appear, depending on which choice you select: Averaged List Math Function Sorted List Look-Up Table Integral External Sliding Window Dual Valve Average Proportion Accumulation Dual Ramp Multi-Proportion Pulse Start CAUTION: Select the mode before entering any other data on an Analog Global Screen. If other information is entered before the mode is selected, there is a chance that the global analog will not perform properly. If data has already been entered and you want to change the mode, you must fi rst clear the screen by using the feature, and then exit to the Global Analog Summary Screen before re-entering data. If the analog input is unavailable, then use 70.0 as a default value. If the input value is not available or invalid, then the value of this Analog Global Look Up Table Mode Screen
global analog will default to this number.