Page 541
12. WCC III INSTALLATION
GUIDE
WCC III Technical Guide
12-45
The following table shows the required load resistor, Data Pattern,
0 % and 100 % programmed values, Jumper setting, Analog Type,
for the Analog Input Screen. For the Thermistor type sensors, there
are no 0 % or 100 % values to program.
Figure 12-36: Analog Input Values
Analog Input Screen Values
Temperature
Sensor
Load
Resistor
(Ohms)
Data Pattern
% Scale
100% Scale
Jumper
Setting
Analog Type
2-Wire Surface
Mount
100
XXX.X
0.0
100.0
0-1
General
0.0
500.0
0-5
General
2-Wire Flush
Mount
301
XXX.X
0.0
100.0
0-1
General
0.0
500.0
0-5
General
3-Wire Flush
Mount
None
XXX.X
0.0
100.0
0-1
General
0.0
500.0
0-5
General
2-Wire Air/Water
100
XXX.X
0.0
100.0
0-1
General
2-Wire Air/Water
49.9
XXX.X
0.0
200.0
0-1
General
Thermistor Flush
Mount
None
XXX.X
Auto
Auto
THERM
Thermistor
Thermistor Duct
6”
None
XXX.X
Auto
Auto
THERM
Thermistor
Thermistor Duct
6”
None
XXX.X
Auto
Auto
THERM
Thermistor
Thermistor
Outdoor Air
None
XXX.X
Auto
Auto
THERM
Thermistor
Analog Input Values