beautypg.com

13b. wcc iii - mcd installation guide, Input/output connections – WattMaster WM-WCC3-TGD-01B User Manual

Page 624

background image

WCC III Technical Guide

13B-12

13B. WCC III - MCD INSTALLATION GUIDE

R & T COMMUNICATIONS LEDs

There are simplistic communication diagnostic LEDs that are
provided next to each one of the RS-485 connectors. The LED
marked “R” stands for “Receive”, and this red LED will fl icker
when data is received from a specifi c satellite controller. The LED
marked “T” stands for “Transmit” and this red LED will LED will
fl icker when data is transmitted by the WCCIII-MCD2 to a specifi c
satellite controller).

10/100 Network ports eth0, and eth1

The main Ethernet port on the WCCIII-MCD2 is named and
labeled “eth0”. This is the primary I/P connection to the WCCIII-
MCD2 device. See page XX for detailed instructions on how to
properly confi gure this network port for proper network access.

The auxiliary (second) Ethernet port on the WCCIII-MCD2 is
named and labeled “eth1”. This port confi guration should never
be changed or reconfi gured by the contractor or end user. It is
meant for direct connection (with a network cross-over cable) to
a Laptop that is to be used for setup, confi guration, updating, and
troubleshooting, or to a dedicated WCC3 computer that would be
set up to run the various WCC3 type programs that connect to the
WCCIII-MCD2 via a network connection.

Each port—etho0 and eth1—has two built in LEDs.

The Left LED is a bi-color Network Speed indicator:

LED Yellow on – Operating as a Gigabit connection (1000 Mbps)
LED Green on – Operating as a 100-Mbps connection.
LED Off – Operating as a 10-Mbps connection.

The Right LED is Link/Activity indicator:

LED Blinking – There is activity on this port.
LED Off – There is no network link established.

Input/Output Connections

Various I/O connections that are on the

Bottom Side of the WCCIII-MCD2 Device

24VAC Power Connector

A two position de-pluggable connection is provided for power
connection to the WCCIII-MCD2 device. The WCCIII-MCD2 is
powered off of dedicated 120VAC to 24VAC@50VA transformer
that WattMaster Controls supplies with each WCCIII-MCD2
device. The 24VAC power de-pluggable connector is considered
to be “polarized” with a 24VAC side and a GND side. Correct
power polarity must be observed.

RS-485 Connectors

The WCCIII-MCD2 device provides four separate RS-485
connections. Each one of these three position de-pluggable
RS-485 connections are distance rated for up to 4000 feet of
communications loop cable when using approved communications
wire. (WM Part # or WM Part #). This communications cable is
described as 18 gauge single pair twisted, with a shield, and drain
wire. The Drain wire (Shield) must be connected between the
WCCIII-MCD2 device and all of the Satellite controllers.

Wiring between the WCCIII-MCD2 and the satellite

controllers:

Basic rule of thumb when wiring communications from the
WCCIII-MCD2 to any and all Satellite connections: Wire “R”
connections to “R” connections, Wire “T” connections to “T”
connections, Wire “SH( SHLD)” connections to “SH (SHLD)”
connections, and there should not be an issue with communications
wiring.

This manual is related to the following products: