WCC III Technical Guide

3-85

WCC3.EXE SCREEN DESCRIPTIONS

BINARY OUTPUT SCREEN

Satellite # 1

BINARY OUTPUT # 3

Description: S1-BO3

Contact Open Message #: 2 off

Contact

Close

Message

#:

1

on

Mode: BINARY

Minimum Off Time: 0 Minutes

Contact Confi guration: Normal Open

Minimum On Time: 0 Minutes

In local set contact set to: OPEN
Controlled by input: L3

Keep On Time: 0 Minutes

Analog Mode setup:

Normal Setpoint: 0

Alternative Setpoint: 0

Hysteresis: 0

Alternative Controlled By ////

HOME for menu

Satellite # _____

Specifi es the number of the satellite you are currently editing.
If you would like to edit a different satellite, simply position the
cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired satellite number, and press

.

Binary Output

Specifi es the summary type to be displayed. Because this is a
“choice” fi eld, a list of available choices will be displayed at the
bottom of the screen:

TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>

Make your selection by pressing the

once for each

choice until the desired point type has been selected, and then
press

. (If you select a point type that is different than

that currently being displayed, the screen will be rewritten with the
appropriate screen and data.)

Description

Enter a description for the output. The description can be up to 10
characters in length. This description will display in the Comments
fi eld on the Binary Output Summary Screen.

Mode: __________

Specifi es the mode type of the input. Because this is a “choice”
fi eld, the list of available choices will be displayed at the bottom
of the screen:

Make your selection by pressing the

once for each

choice until the desired point type has been selected, and then press

.

Contact Confi guration: __________

Specifi es the type of confi guration. Because this is a “choice” fi eld,
the list of available choices will be displayed at the bottom of the
screen:

Contact Open Message #: ____

Contact Closed Message #: ____

Specifi es a pair of message numbers, one for the contact open state
and the second for the contact closed state. These numbers refer
to a message on the On/Off Units Message Screen. For example,
message #1 might be “Fan On” and message #2 “Fan Off.” If you
want the message on the Control Output Summary Screen to be
“Fan On” when the satellite contact is closed, enter “#1” as the
contact closed message etc.

Binary Output Screen’s WCC III Logical Address is XXXOYY, where XXX = Satellite Address #,

O = Binary Output, YY = Binary Output #