Wcc3.exe screen descriptions, Binary global screen compare mode, Binary global compare mode screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 279
WCC III Technical Guide
3-165
WCC3.EXE SCREEN DESCRIPTIONS
Mode: 2 Compare
Specifi es the mode used to generate the ON or OFF value of the
binary global. Because this is a choice fi eld, the following list of
available choices will be displayed at the bottom of the screen:
Alarm-by-Class, One Shot, Clock, Delay, PWM, Lead-Lag> Make your selection by pressing the once for each choice until the desired mode has been selected, and then press . Whenever you change modes, you must fi rst clear the existing screen by using the feature. The compare mode generates the ON or OFF value of the binary The Compare Screen allows the WCC III system to do “greater global #2 (GB2) to go ON if the outside air enthalpy is less than the Value is ON if 1A4 > 2A5 Default value: 25 20 In the above example, the global binary will be ON when the value Entering a Constant Number If you want to enter a constant for one of the two values, leave Value is ON if 1A4 > ------ Default value: 25 20 In the above example, the value of the global binary will be ON BINARY GLOBAL SCREEN COMPARE MODE BINARY Global #: _10 name is GB 10 Description: Example On Message #: 1 On Mode: 2 Compare Off Message #: 2 Off Value is ON if 1A4 > 2A5 Hysteresis: ± ---- Default value : 25.000 20.000 0.000 -------------------ALARM-------------------- Set Condition: None Type: 0 Message: 0 HOME for menu Binary Global Screen’s WCC III Logical Address is GBXXX, where GB = Global Binary and XXX = Global Binary Address Binary Global Compare Mode Screen
global depending on how one analog value compares to another
analog value.
than/less than” logic. The ON or OFF value of the binary global
is determined by one numerical value being [equal to], [greater
than or equal to], [less than], or [less than or equal to] another
numerical value. For example, the WCC III system could monitor
the enthalpy (total heat content) of the outside air and the return
air and select he air stream with the lowest heat content to be used
for cooling. The Compare Screen could be used to cause binary
return air enthalpy, indicating that the outside air should be used
for cooling. The WCC III system could then be programmed to
open the outside air damper and lose the return air damper when
GB2 is ON.
of 1A4 (analog input #4 on satellite controller #1) is greater than
2A5 (analog input #5 on satellite controller #2). If the analog value
is unavailable, the system will use the default value below the
analog value. For example, if satellite controller #1 was off-line,
the value for analog input #4 on satellite controller would default
to 25.
the top blank and enter a number in the default space as shown
below:
when 1A4 is greater than 20.
In Local Set this global defaults to Off.