WCC III Technical Guide
3-165
WCC3.EXE SCREEN DESCRIPTIONS
Mode: 2 Compare
Specifi es the mode used to generate the ON or OFF value of the 
binary global. Because this is a choice fi eld, the following list of 
available choices will be displayed at the bottom of the screen:
Alarm-by-Class, One Shot, Clock, Delay, PWM,  Lead-Lag> Make your selection by pressing the   once for each  choice until the desired mode has been selected, and then press  . Whenever you change modes, you must fi rst clear the  existing screen by using the   feature. The compare mode generates the ON or OFF value of the binary  The Compare Screen allows the WCC III system to do “greater  global #2 (GB2) to go ON if the outside air enthalpy is less than the  Value is ON if  1A4   >  2A5 Default value:   25     20 In the above example, the global binary will be ON when the value  Entering a Constant Number If you want to enter a constant for one of the two values, leave  Value is ON if  1A4   >  ------ Default value:   25     20 In the above example, the value of the global binary will be ON   BINARY GLOBAL SCREEN COMPARE MODE                     BINARY Global #: _10   name is GB 10 Description: Example        On Message #: 1 On Mode: 2 Compare        Off Message #: 2 Off Value is ON if    1A4 > 2A5 Hysteresis: ± ----  Default value :   25.000 20.000     0.000          -------------------ALARM--------------------     Set Condition: None   Type: 0 Message: 0 HOME for menu Binary Global Screen’s WCC III Logical Address is GBXXX, where GB = Global Binary and XXX = Global Binary Address Binary Global Compare Mode Screen
global depending on how one analog value compares to another 
analog value.
than/less than” logic. The ON or OFF value of the binary global 
is determined by one numerical value being [equal to], [greater 
than or equal to], [less than], or [less than or equal to] another 
numerical value. For example, the WCC III system could monitor 
the enthalpy (total heat content) of the outside air and the return 
air and select he air stream with the lowest heat content to be used 
for cooling. The Compare Screen could be used to cause binary 
return air enthalpy, indicating that the outside air should be used 
for cooling. The WCC III system could then be programmed to 
open the outside air damper and lose the return air damper when 
GB2 is ON.
of 1A4 (analog input #4 on satellite controller #1) is greater than 
2A5 (analog input #5 on satellite controller #2). If the analog value 
is unavailable, the system will use the default value below the 
analog value. For example, if satellite controller #1 was off-line, 
the value for analog input #4 on satellite controller would default 
to 25.
the top blank and enter a number in the default space as shown 
below:
when 1A4 is greater than 20.
In Local Set this global defaults to Off.