4. SCUSCR.EXE SCREENS
WCC III Technical Guide
4-35
Single Duct Globals and Mode of Operation Screens
Force Damper to Maximum Setpoint when GB(X)
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to have maximum 
airfl ow in the conditioned zoned space. Such forced overrides 
could include Global binary determinations for morning warmup, 
troubleshooting, air balancing, CO2 reduction, pre-cooling or pre-
heating for a meeting room, smoke detection (Remember that the 
WCC III is not rated for fi re life safety) etc. On a Global force 
mode it will be possible to force multiple VAVZONE boxes open or 
closed with a single global command. (Ignores Airfl ow Reading)
Force Damper to Minimum Setpoint when GB(X)
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to have minimum 
airfl ow in the conditioned zoned space. Such forced overrides 
could include Global binary determinations for troubleshooting, 
air balancing, night set back, smoke detection (Remember that the 
WCC III is not rated for fi re life safety) etc. On a Global force 
mode it will be possible to force multiple VAVZONE boxes open or 
closed with a single global command. (Ignores Airfl ow Reading)
Force Damper to Re-Calibrate when GB(X)……..
The VAVBOX TUC-2R controller damper can be globally forced 
to one of several positions with the use of Global Binaries. There 
may be times at which the end user will want to re-calibrate the 
actuator on the VAVBOX. Such forced overrides could include 
troubleshooting and air balancing.
Remember that there may be a mechanical problem with the 
actuator or air valve damper, and you should always try to re-
calibrate the actuator before determining if the actuator is actually 
bad or not.
Force Energy Management { EMS } Mode when 
GB(X)…
The VAVBOX TUC-2R controller damper can be globally forced 
into an Energy Management Mode, typically during peak load 
demand periods, during this time the Terminal Unit Controller 
(TUC-2R) will increase the cooling setpoint and also decrease the 
heating setpoint by 2 ºF.
Duct Temperature can be read from Global 
Analog……..
A Duct Air Temperature Sensor can be connected to the VAVBOX 
TUC-2R or it can be read from a Global Analog. It should be 
mounted in the supply duct close to the terminal unit where the 
VAVBOX controller is installed. This sensor can be used for 
monitoring purposes in place of the Duct Temperature Broadcast 
from the MCD, otherwise the Duct Temperature will always read 
the same as the Space Temperature.
NOTE:
1.) All temperature sensors must be Thermistor Type
III which provide 77.0 ºF @ 10K Ohms Resistance.
2.) The Duct Temperature Broadcast from the MCD must be in 
a X,XXX format, no decimal place.
Space Temp Sensor Calibration Offset
There is an option to change the calibration of a thermistor sensor 
(Usually due to the position or location of the thermistor sensor) 
a few degrees plus or minus from the actual temperature that the 
thermistor sensor is actually reading. Acceptable values in this 
fi eld are numerical with both positive and negative(+/-) values of 0 
to 99. These values are in degrees Fahrenheit.
SYSTEM DIAGNOSTICS
Powerup Count:
This is the number of times that the TUC-2R controller has reset 
or has been repowered since the last time the powerup counter was 
cleared.
Enable Counts:
The enable count fi eld is where you would enter a 1 to Clear/
Disable the powerup counter. You must set this value back to “0” 
to enable the powerup counter to work again.