Scuscr.exe screens, Wcc iii vav box iii tenant override logs – WattMaster WM-WCC3-TGD-01B User Manual
Page 324

WCC III Technical Guide
4-14
4. SCUSCR.EXE SCREENS
Damper Control
The damper position is calculated by the mode and demand from 
the space sensor. Included in this calculation is an Integral function. 
This prevents the damper/airfl ow from stagnating at a position 
somewhere above the setpoint because the supply air temperature 
or duct pressure isn’t quite enough to satisfy the space at the 
currently calculated proportional position. The Integral causes the 
calculation to keep adding a small amount of the proportional error 
back into the damper/airfl ow position each time a new position is 
calculated. The amount the Integral adds back in is user adjustable. 
This value is presented as a number between 0.0 and 100.0. 
That means that if the integral is less than 10.0, you are adding a 
percentage from 0 to 100% of the error back into the calculation. 
If you increase the Integral above 10, you are adding more than 
100% back in.
With just proportional control, a 1 ºF error would cause a 50% 
increase in damper/airfl ow if the Integral is not included. (1 °F is 
half of the 2 ºF Proportional Window.) 
If you had set the Integral to 10, the calculation would add 2% to 
the current damper/airfl ow calculation each time. The calculation 
occurs once every 10 seconds, so it would take a little over 4 
minutes to reach the programmed 100% maximum.
Example:
1. 50% Remaining / 2% Integral = 25 Moves to get to a 100% 
Maximum.
2. 25 Moves times 10 seconds = 250 seconds or a little over 4 
minutes to reach the 100% maximum damper/airfl ow position.
Of course, different space temperature errors and different Integral 
values cause this calculation to operate slower or faster. It is up to 
the user to determine the optimum setting that provides the tightest 
temperature control without causing the damper to continue to 
hunt or modulate, causing premature wear of the actuator gears 
and motor.
On pressure dependent terminal units, the damper position is 
maintained to within ± 3% of the calculated position. No attempt 
is made to position the damper exactly on the calculated position. 
This reduces wear and tear on the actuator gears and motors, and 
the amount of airfl ow involved is not affected by that small amount 
of damper error.
On pressure independent terminal units, the airfl ow is maintained 
to within roughly 3% of the terminal unit size constant but no 
tighter than 16 CFM on the smallest terminal units. The actual 
control window is based on the formula:
Window = Terminal unit size X Square Root (1 / 750), where 
Terminal unit size refers to the total rated CFM of the terminal 
unit.
This sliding window allows the control to be much tighter on the 
smaller terminal units than can be achieved on the larger terminal 
units as far as CFM readings. On a large terminal unit, 25 CFM 
may not be noticeable, but on a small terminal unit, 25 CFM may 
be more than the minimum airfl ow setting for the space.
If the pressure sensor is disconnected or fails on a pressure 
independent terminal unit, the damper position goes to 100% open 
and the VAV/Zone controller generates a General TUC Alarm to 
alert the user that a failure has occurred. 
On either type of terminal unit, a space sensor failure will force the 
damper to position itself to the 45% position and it will not change 
until the sensor is repaired or replaced.
Tenant Override Logs
If you require tenant billing for push-button override usage, the 
MCD has the ability to track the amount of override time generated 
by each space sensor equipped with push-button override.
NOTE:
The VAVBOX TUC-2R controller will go into an
override condition for the user programmed amount of time 
when this button is pushed even if the unit is already in a 
occupied condition.
Storing and retrieving these logs requires a dedicated front end 
computer running the WCC III Trendlog front-end software 
program. No other method exists for retrieving these logs. That 
means that all of your VAV/Zone controllers will be connected 
together on the communications loop and the loop will be terminated 
at a Satellite device which is connected to another communications 
loop that is terminated at an on-site MCD computer. The tenant 
logs are kept on the dedicated job site computer’s hard drive. The 
only limitation to the number of logs stored is the capacity of the 
hard drive on the computer to which it is being logged.
NOTE:
There is also a Tenant Override software that can
be programmed that tenants can use to turn on multiple 
zones(among other things) at once without having to use the 
push button override on the space sensor. See Section 6 of the 
WCC III manual for detailed operation of this program.
WARNING:
This WCC III - MCD computer must be on 24
hours a day, 7 days a week, running the Backtask.exe software 
in order for tenant logging to be tracked. The tenant logs are 
kept on the dedicated end user job site computer’s hard drive. 
The only limitation to the number of logs stored is the capacity 
of the hard drive on the computer they are being logged to.
WCC III VAV BOX III Tenant Override Logs
