Figure 4-15: Parallel Fan Powered - Pressure Dependent Setpoint Screen
Parallel Fan Powered Pressure Dependent Setpoint Screen
Occupied Cooling Setpoint
This is the cooling temperature setpoint that you wish to control the 
Zone’s space temperature to during occupied times when the main 
air handler is turned on. The damper will modulate the actuator to 
control the temperature in the space.
Occupied Heating Setpoint
This is the heating temperature setpoint that you wish to control the 
Zone’s space temperature to during occupied times when the main 
air handler is turned on. The damper will modulate the actuator to 
control the temperature in the space.
Unoccupied Cooling Setpoint
This is the cooling temperature setpoint that you wish to control 
the Zone’s space temperature to during unoccupied times when 
the main air handler is turned on. The damper will modulate the 
actuator to control the temperature in the space.
Unoccupied Heating Setpoint
This is the heating temperature setpoint that you wish to control 
the Zone’s space temperature to during unoccupied times when 
the main air handler is turned on. The damper will modulate the 
actuator to control the temperature in the space.
Maximum Sensor Slide Effect on Setpoints
Enter a value of 0 to 5 that corresponds to 0 to 5 degrees F. This 
allows the tenant to remotely adjust the setpoint in his or her zone. 
There has to be a sensor with a slide pot on it in order for this to 
work, and this sensor must be properly wired back to the TUC-2R 
controller.
Pushbutton Override Duration
Enter a value of 0 to 24 that corresponds to 0 to 24 hours for the 
override to have in effect. This allows the tenant in the space to 
remotely turn the zone from unoccupied mode to override mode.
NOTE:
The VAVBOX controller will go into an override
condition for the user programmed amount of time when 
this button is pushed even if the unit is already in a occupied 
condition. The maximum amount of time that can be 
programmed may vary on different types of software.
Damper Control Integral {Ki}
The “Damper Control Integral {Ki}” is the speed at which the 
control loop within the electronic controls that is controlling the 
electronic actuator that will actually modulate the damper for 
temperature control / CFM control. 100 is fastest while 1 is slowest. 
Normally should be set to 1.