Wcc3.exe screen descriptions, Analog input screen, Wcc iii technical guide 3-32 – WattMaster WM-WCC3-TGD-01B User Manual
Page 146
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-32
V
OUT
GND
+V
ATI
1 TO 8
1 TO 8
NO
LOAD
RESISTOR
Input Jumper must be set to THERM
There are berg jumpers that are under the SAT III cover that must be set.
JOX corresponds to X = 1 to 8 for the Analog Input jumper.
Example:
JO1 is for Analog Input #1
JO8 is for Analog Input #8
An Input Load Resistor must not be used as a pull down resistor, because
the required 5 volts comes from the Thermistor pull up resistor.
RX corresponds to X = 1 to 8 for the Analog Input load resistor.
Example as follows:
R1 is for Analog Input #1 R4 is for Analog Input #4
R6 is for Analog Input #6 R8 is for Analog Input #8
Testing with a voltmeter:
Measure from ATI to GND. You should get a voltage measurement that
corresponds to the ON / OFF. 5.0 Volts DC equals OFF
The V-Out output is not used for this application.
JOX
THERM
0-10V
0-5V
0-1V
CONNECTIONS ON
SAT III CONTROLLER
ANALOG INPUT AS AN ANALOG SWITCH INPUT - Thermistor Scaling Factor
0-1V INPUT
ANALOG INPUT SCALING - From Sat Analog Input Screen
Description:
Type: Analog General
Pattern for values associated with this input: xxx.x
Units @ 0 % Scale 0.0 Deg F Units of measure message #: 1
@ full scale: 100.0 Deg F Filter time constant: 0 Seconds
===========Binary Setpoint ===========
OFF above 80.0 Deg F On Message #: ON
ON below 50.0 Deg F Off Message #: OFF
SWITCH
BY OTHERS
V
OUT
GND
ATI
1 TO 8
NO
LOAD
RESISTOR
Input Jumper must be set to THERM
There are berg jumpers that are under the SAT III cover that must be set.
JOX corresponds to X = 1 to 8 for the Analog Input jumper.
Example:
JO1 is for Analog Input #1
JO8 is for Analog Input #8
An Input Load Resistor must not be used as a pull down resistor, because
the required 5 volts comes from the Thermistor pull up resistor.
RX corresponds to X = 1 to 8 for the Analog Input load resistor.
Example as follows:
R1 is for Analog Input #1 R4 is for Analog Input #4
R6 is for Analog Input #6 R8 is for Analog Input #8
Testing with a voltmeter:
Measure from ATI to GND. You should get a voltage measurement that
corresponds to the ON / OFF. 5.0 Volts DC equals OFF
The V-Out output is not used for this application.
JOX
THERM
0-10V
0-5V
0-1V
CONNECTIONS ON
SAT III CONTROLLER
ANALOG INPUT AS AN ANALOG SWITCH INPUT - Thermistor Scaling Factor
0-5V INPUT
ANALOG INPUT SCALING - From Sat Analog Input Screen
Description:
Type: Analog General
Pattern for values associated with this input: xxx.x
Units @ 0 % Scale 0.0 Deg F Units of measure message #: 1
@ full scale: 500.0 Deg F Filter time constant: 0 Seconds
===========Binary Setpoint ===========
OFF above 400.0 Deg F On Message #: ON
ON below 100.0 Deg F Off Message #: OFF
+V
1 TO 8
SWITCH
BY OTHERS
Analog Input Screen