Wcc3.exe screen descriptions, Modified pid programs screen – WattMaster WM-WCC3-TGD-01B User Manual
Page 230
WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-116
MODIFIED PID PROGRAMS SCREEN
Modifi ed PID Mode
Proportional Gain:
This defi nes the Proportional Gain of the modifi ed PID formula.
Integrator Time:
This defi nes the Integrator Time of the modifi ed PID formula.
Derivative Time:
This defi nes the Derivative Time of the modifi ed PID formula.
Maximum Integrator Value:
This defi nes the absolute maximum the Integrator Value can be.
Maximum Derivative Value:
This defi nes the absolute maximum the Derivative Value can be.
Proportional Setpoint Factor:
This defi nes the Proportional Setpoint Factor of the modifi ed PID
formula.
Anti-Winding Time:
This defi nes the Anti-Winding Time of the modifi ed PID formula.
Noise Factor:
This defi nes the Noise Factor of the modifi ed PID formula.
USE DEFAULT MODIFIER
This commands the WCC3 to set the Proportional Setpoint Factor,
Anti-Winding Time, and Noise Factor to the default value.
Current Proportional:
This shows the current Proportional portion of the output.
Current Integrator:
This shows the current Integral portion of the output.
Current Derivative:
This shows the current Derivative portion of the output.
Current Output:
This shows the current output value.
Current Sampling:
This shows the current sampling value.
Current Output:
This shows the current calculated output value before the limit is
adjusted.
Modified PID Programs Screen