Wcciii - mcd - rear view, Typical system configuration with sat 3f, Wcc iii technical guide 15-19 – WattMaster WM-WCC3-TGD-01B User Manual
Page 711
WCC III Technical Guide
15-19
15. SAT 3C/D/F INSTALLATION
Typical System Configuration with SAT 3F
8
7
SAT ADDRESS
2
1
4
8
A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.
A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.
CURRENT
INPUT
THERMISTOR
INPUT
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
0 - 10V
0 - 1V
0 - 5V
0 - 10V
THERM
0 - 1V
0 - 5V
THERM
0 - 1V
0 - 5V
0 - 10V
THERM
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX
0-15VDC
OUTPUT
MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY
TO THE REST OF SAT III
ON SAT LOOP 1 TO 60
24VAC
LINE
VOLTAGE
24VAC
LINE
VOLTAGE
TO THE REST OF SAT III
ON SAT LOOP 61 TO 120
TO THE REST OF SAT III
ON SAT LOOP 121 TO 180
TO THE REST OF SAT III
ON SAT LOOP 181 TO 239
(MASTER COMMUNICATIONS DEVICE)
OPTIONAL EXPANSION
TO THE ISP
(INTERNET SERVICE PROVIDER)
CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED DSL / CABLE MODEM / ROUTER
ETHERNET
CABLE
WCCIII - MCD - Rear View
120V LINE
VOLTAGE
TYPICAL SYSTEM CONFIGURATION WITH SAT 3F
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICD
Communications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS
1
STATUS
LOCAL SET
16
4
2
8
64
32
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
CONNECTION
FOR TUC LOOP
1 TO 16 UNITS
TO THE REST OF SAT III
ON SAT LOOP 1 TO 60
24VAC INPUT FOR UPS LOSS
OF POWER DETECTION
UP TO 4000 FT. OF
COMMUNICATIONS
WIRE MAX PER LOOP.
PRINTER PORT - LASER
PRINTER NOT SUPPORTED
ETHERNET
CABLE
OE217
F
OE320-23
Display
Override
OVERRIDE
ALARM
STAT
THERM
4-20mA
0-10V
0-5V
COMM
OPTION 4
OPTION 3